Laserfiche WebLink
SWRC-B,January 2002 <br />SPILL/OVERFILL CONTAINMENT BOXES <br />Page 2. <br />Facility is Not Equipped With Spill/Overfill Containment Boxes: <br />Spill/Overfill Containment Boxes are Present, but were Not Tested: <br />Test Method Developed By: Spill Bucket Manufacturer Industry Standard Professional Engineer <br />Other (Specify) <br />Test Method Used: ❑ Pressure F Vacuum Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used: Equipment <br />Spill Box # REGULAR Spill Box # PREMIUM <br />Resolution: <br />Spill Box # <br />Spill Box # <br />Bucket Diameter: <br />12 <br />12 <br />Bucket Depth: <br />14 <br />14 <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />10 <br />10 <br />Test Start Time: <br />1010 <br />1010 <br />Initial Reading (RI ): <br />12 <br />12.5 <br />Test End Time: <br />1110 <br />1110 <br />Final Reading (RF ): <br />12 <br />12 .5 <br />Test Duration: <br />60 mins <br />60 mins <br />Change in Reading (R F - RI) <br />0 <br />0 <br />Pass/Fail Threshold or <br />Criteria: <br />1/811- 60mins <br />1/811- 60mins <br />Test Result: <br />El Pass E] Fail <br />z Pass 1:1 Fail <br />D Pass 1:1 Fail <br />E]Pass El Fail <br />Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />manufacturer OPW <br />