Laserfiche WebLink
TABLE 3 <br /> AST Capacity <br /> ST. JOSEPH'S MEDICAL CENTER <br /> 1800 North California Street, Stockton, California <br /> Tank Location Type Capacity Contents Active <br /> ID (Gallons) <br /> FIXED OIL STORAGE <br /> South of Main Generator Double Wall AST <br /> 1 Room —supplies (UL 2085) 8,000 Diesel Yes <br /> enerator 109 A & B <br /> Main Generator Room — Double Wall AST <br /> 2 supplies generator (UL 142) 350 Diesel Yes <br /> Dou <br /> 109A & B <br /> Main Generator Room — Double Wall AST <br /> 3 supplies generator (UL 142) 350 Diesel Yes <br /> Dou <br /> 109A & B <br /> West of Main Generator Aboveground <br /> 4 Room —supplies Double Wall Belly 59 Diesel Yes <br /> generator 109 C Tank <br /> UL 142 <br /> East of Laboratory— Aboveground <br /> 5 supplies generator Double Wall Belly 284 Diesel Yes <br /> 109 HC Tank UL 142 <br /> Generator Room — Aboveground <br /> 6 supplies generator 109 P Double Wall Belly 3,000 Diesel Yes <br /> Pavilion Tank Tank UL 142 <br /> East of Behavioral Health Aboveground <br /> 7 Care Center(2510 N Double Wall Belly 250 Diesel Yes <br /> California St)—supplies Tank (UL 142) <br /> generator BHC <br /> TOTAL: 12,293 <br /> PORTABLE OIL STORAGE <br /> _ Hazardous Waste Waste Oil and <br /> Storage Room Steel Drums 55 (x8) various haz. Yes <br /> waste <br /> Main Generator Room Generator motor 84 (x2) Used Motor Oil Yes <br /> (109 A & B) (oil filled equipment) <br /> - Generator Room (109 P) Generator motor 84 Used Motor Oil Yes <br /> (oil filled equipment) <br /> TOTAL: 692 <br /> TOTAL OIL STORAGE CAPACITY: Approximately 12,985 gallons <br /> `N e:The portable oil storage is variable <br />