Laserfiche WebLink
Form 1 <br /> Source Test Tesults <br /> Static Leak Test <br /> Date: 08/28/2000 Time: 08:00 Application No. <br /> GDF Name and address: 19976 1399 N. MAIN ST. <br /> Stage II system (check one): Vapor Balance [ ] Single Hose M.P.D. [ ] <br /> Vacuum Assist [X ] Type: GILBARCO <br /> Stage I type (check one): Two point [X ] Manifolded? Yes [X ] <br /> Coaxial [ ] No [ 1 <br /> Tank# 1 2 3 <br /> Product grade RUL MUL PUL <br /> Actual tank capacity (gallons) 9995 9995 9995 29985 <br /> Gasoline volume (gallons) 3542 1822 2211 7575 <br /> Ullage (gallons) 6453 8173 7784 22410 <br /> Initial pressure of UST, inches H2O 0 <br /> Number of nozzles served by tank 4 4 4 12 <br /> Test location: (A) Stage I vapor <br /> coupler of(B) Stage II riser B B B 2.00 <br /> Initial Pressure, inches H2O (2.0) 2.00 <br /> Pressure after 1 min. (inches H2O) 2.00 <br /> Pressure after 2 min. (inches H2O) 2-00 <br /> Pressure after 3 min. (inches H2O) 2.00 <br /> Pressure after 4 min. (inches H2O) 2.00 <br /> Final Pressure after 5 min. (inches <br /> H2O) <br /> 2.00 <br /> Allowable Final Pressure: Table 1 A, <br /> Table 1B, Equations 9.1, 9.2 1.9; <br /> Test Status [Pass or Fail] Pass <br /> Tests Conducted By: ACHAND <br /> Test Company: TANKNOLOGY Date of Tests: 08/28/2000 <br /> Tests Witnessed By: GRAIG L.MITCHELL <br />