Laserfiche WebLink
NDE ENVIROMENTAL CORPORATION <br />Stage II Vapor Recovery Test Results Form <br />Air / Liquid Ratio Test For Vacuum Assist Systems <br />Site Information: <br />7 -ELEVEN 19976 <br />MARKET 2235 <br />MANTECA, CA. 95336 <br />Ambient Conditions Corrected <br />Pressure Temp. Air Volum <br />Inches Hg Degrees F (ft -3) <br />Calculated A/L Ratio <br />A/L Average <br />Final <br />Results <br />Pass/Fail <br />Work Order #: <br />2205319 <br />Date: 07/27/98 <br />Technician: DAVID MATHIE <br />9.4 <br />Nozzle # <br />Product <br />Product Flow Rate Calculation <br />Gallons (g) Time (s) Flowrate <br />Dispensed Seconds G.P.M. <br />Air Volume Metered (ft^3) <br />Initial Final Volume <br />Reading Reading Metered <br />Ambient Conditions Corrected <br />Pressure Temp. Air Volum <br />Inches Hg Degrees F (ft -3) <br />Calculated A/L Ratio <br />A/L Average <br />Final <br />Results <br />Pass/Fail <br />7.534 <br />48.00 <br />9.4 <br />3887.44 <br />3888.38 <br />0.940 <br />0.93 <br />4 <br />REG <br />0.93 <br />Fail <br />7.505 <br />48.00 <br />9.4 <br />3888.38 <br />3889.35 <br />0.970 <br />0.97 <br />4 <br />PREMIUM <br />0.97 <br />Fail <br />7.508 <br />47.00 <br />9.6 <br />3889.35 <br />3890.32 <br />0.970 <br />0.97 <br />4 <br />PLUS <br />0.97 <br />Fail <br />Type of System Tested: Gilbareo Vapory <br />