Laserfiche WebLink
INDIVIDUAL TANK INFORMATION AND TEST RESULTS <br /> 11111 1P TankrK*2gy <br /> TEST DATE:07/13/04 8900 SHOAL CREEK,BUILDING 200 WORK ORDER NUMBER2231561 <br /> CLIENT:7-ELEVEN, INC. AUSTIN,TEXAS 78757(512)451-6334 SITE:7-ELEVEN # 19976 MKT 2237 <br /> TANK INFORMATION <br /> Tank ID: #1 1 Tank manifolded: NO Bottom to top fill in inches: 142.0 <br /> Product: REG UNLEAD Vent manifolded: NO Bottom to grade in inches: 151.0 <br /> Capacity in gallons: 14,781 Vapor recovery manifolded: YES Fill pipe length in inches: 51.4 <br /> Diameter in inches: 90.00 Overfill protection: YES Fill pipe diameter in inches: 4.0 <br /> Length in inches: 543 Overspill protection: YES Stage I vapor recovery: DUAL <br /> Material: DW FIBERG Installed: ATG Stage II vapor recovery: ASSIST <br /> CP installed on: <br /> COMMENTS <br /> TANK TEST RESULTS Test Method:VacuTect LEAK DETECTOR TEST RESULTS Test method: FTA <br /> Start(in) End(in) <br /> Dipped Water Level: New/passed Failed/replaced New/passed Failed/replaced <br /> Dipped Product Level: L.D.#1 L.D.#1 L.D.#2 L.D.#2 <br /> Probe Water Level: Make: RED JACKET <br /> Ingress Detected: Water Bubble Ullage Model: FX1V <br /> Test time: S/N: 309017605 <br /> Inclinometer reading: Open time in sec: 2.00 <br /> Holding psi: 24 <br /> VacuTect Test Type: NOT Resiliency cc: 130 NOT <br /> VacuTect Probe Entry Point: TESTED Test leak rate ml/m: 189.0 TESTED <br /> Pressure Set Point: Metering psi: 10 <br /> Tank water level in inches: Calib. leak in gph: 3.00 <br /> Water table depth in inches: Results: PASS <br /> Determined by(method): <br /> Result: <br /> COMMENTS <br /> COMMENTS <br /> LINE TEST RESULTS Test type: TLD-1 <br /> LINE A B C D <br /> Material: ENVIRON <br /> Diameter(in): 1.5 <br /> Length (ft): 45.0 <br /> Test psi: 50 <br /> Bleedback cc: 125 <br /> Test time (min): 60 NOT NOT NOT <br /> Start time: 10:21 TESTED TESTED TESTED <br /> End time: 11:21 <br /> Final gph: 0.000 <br /> Result: PASS <br /> Pump type: PRESSURE <br /> Pump make: FE PETRO <br /> COMMENTS Impact Valves Operational: YES <br /> Printed 07/20/2004 08:29 <br />