Laserfiche WebLink
CERTIFICATE OF UNDERGROUND STORAGE TANK SYSTEM TESTING <br /> NDE ENVIRONMENTAL CORPORATION NDE <br /> 8906 WALL STREET, SUITE 306 <br /> AUSTIN, TEXAS 78754 ME <br /> (512) 719-4633 <br /> FAX (512) 719-4986 <br /> TEST RESULT SITE SUMMARY REPORT <br /> TEST TYPE: VPLT <br /> TEST DATE: October 23, 1996 WORK ORDER NUMBER: 966668 <br /> CLIENT: THE SOUTHLAND CORPORATION SITE: 7-ELEVEN 19976 <br /> 19033 WEST VALLEY HWY. , D-104 MARKET 2235 <br /> KENT, WA 98032 1399 N. MAIN ST <br /> MANTECA, CA 95336 <br /> ATTN: BOB DENINNO <br /> The following tests were conducted at the site above in accordance with all applicable portions of Federal, NFP A and local regulations. <br /> Tank Tests <br /> TANK TANK VOLUME ULLAGE <br /> TANK PRODUCT CAPACITY DIAMETER TANK CHANGE RESULT <br /> NUMBER (Gallons) (Inches) RESULT (gph) <br /> 1 PREMIUM 10,000 95.00 PASS 0.017 PASS <br /> 2 PLUS 10,000 95.00 PASS 0.017 PASS <br /> 3 REG UNLEAD 10,000 95.00 PASS 0.018 PASS <br /> Line and Leak Detector Tests <br /> VOLUME CHANGE LINE RESULT LEAK LEAK <br /> TANK (P=pass, F=fail <br /> PRODUCT (gph) DETECTOR DETECTOR <br /> NUMBER A B C D 1=inconclusive)A B C D PRESENT RESULT <br /> 1 PREMIUM 0.008 P YES PASS <br /> 2 PLUS 0.006 P YES PASS <br /> 3 REG UNLEAD 0.010 P YES PASS <br /> NDE appreciates the opportunity to serve you,and looks forward to working with you in the future. Please call any time,day or night,when you need us. <br /> NDE Customer Service Representative: Test conducted <br /> JERRY BELLOLI ANEIL CHAND <br /> Reviewed: ��jZ�.�'�y�F'ls Technician ertification Number: . <br />