Laserfiche WebLink
4 . The plan do not indicate weather the piping will slope to <br /> the monitored piping sump. The piping must be sloped back <br /> to the sump . Please indicate . <br /> 5 . If the monitoring system is to be equipped with positive <br /> automatic shut off it must alarm when liquid is sensed, <br /> when the probe malfunctions, or is disconnected. <br /> 6 . The tank construction must include striker plates below <br /> each opening. Provide information in regards to tank <br /> construction. <br /> If you have any questions in regards to this please call me at <br /> (209) 468-0332 . <br /> Ernest M. Fujimoto, M.D. , M. P .H. <br /> Actin Health Officer <br /> Robert McClellon R.E.H.S . <br /> Environmental Health Division <br />