Laserfiche WebLink
C, l ,' 2 7%8'3 1Z _t F' . 10 <br /> S?�1v JOA.QU2N Iw.00AT. F�inr.T!-I D>= STRICT <br /> SAMPLING PROTOCAL FOR ROUTINE TANK RE110VALS <br /> The following represents minimum sampling criterion required for closure compliance. If <br /> contamination is documented during closure, an Unauthorized Release notification must be <br /> filled out and submitted to SJLHD within 5 days. Section 2652, CLIC. <br /> WATER NOT PRESENT IN THE TANK PIT <br /> TANK SIZE MINIMUM NUMBER OF LOCATION OF SOIL SAMPLES <br /> ----- SOIL SAMPLES - `-- - <br /> Less than 1000 gallons ONE per tank Fill or pump and of tank <br /> 1000 - 10,000 gallons TWO per tank One at each end of tank <br /> 10,001 gallons and up THREE OR MORE Ends and Middle or <br /> per tank generally spaced along <br /> the lent h of the tank <br /> Piping ONE EVERY 20 LINEAL FEET <br /> WATER IS PRESENT IN TANK PIT <br /> TANK SIZE MINIMUM NO. OF LOCATION OF SOIL MINIMUM NUMBER <br /> SOIL SAMPLES SAMPLES OF WATER SAMPLES <br /> 10,000 GALLONS From wall next to <br /> OR LESS tank ends at soil/ <br /> (Single Tank) TWO groundwater ONE <br /> interface <br /> GREATER THAN From wall next to ONE <br /> 10,000 GALLONS tank ends at soil/ <br /> OR groundwater <br /> TANK CLUSTER FOUR interface <br /> a -- <br /> EH 23 047 12/88 <br />