Laserfiche WebLink
SANJ O A Q U I N avironmental Health Department <br /> -CoUNrY <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> WATERLOO FOODMART 4315 E WATERLOO RD, STOCKTON April 10, 2018 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 201 CCR 2712(b) Failure to maintain monitoring, maintenance, and follow up action records. <br /> The facility failed to address all the alarms from the attached alarm history on the 5/15/17, 6/28/17, 7/24/17, <br /> 8/25/17, 9/7/17, 10/9/17, 11/16/17, 12/4/17, 1/23/18, 2/9/18, 3/5/18, and 4/3/18 designated operator (DO) monthly <br /> inspection reports and failed to check that they were responded to appropriately. The alarms that haven't been <br /> addressed include: <br /> 1) On the 5/15/17 DO report: L11 Disp 1/2 brine alarm on 4/24/17; L12 Disp 3/4 brine alarm on 4/27/17 and 5/5/17; <br /> L13 Disp 5/6 brine alarm on 4/18/17; L14 Disp 7/8 brine alarm on 4/18/17; L15 87 STP sump annular space alarm <br /> on 5/15/17. According to the 5/15/17 DO report, the report indicated that the"alarms on 5/15/17 were due to low <br /> brine, fluid has been removed and alarms were ok."This type of brine sensors do not have a high liquid alarm, and <br /> should not have fluids removed. Please provide clarification on actions taken on this DO report. <br /> 2) On the 6/28/17 DO report: L14 UDC 7/8 brine alarm on 6/28/17 indicates alarm is still on, and has not been <br /> addressed; L18 Vent annular space alarm on 6/19 indicates alarm is still on, and has not been addressed. <br /> 3) On the 7/24/17 DO report: L6 91 annular high liquid alarm on 7/23/17 was still on, and has not been addressed; <br /> L11 dispenser 1/2 brine alarm on 7/22/17 indicates it was still on, and hasn't been addressed; L18 vent annular <br /> space alarm on 6/19/17 indicates it was still on due to leaking brine, and has not been addressed. <br /> 4) On the 8/25/17 DO report: L11 dispenser 1/2 brine alarm since 7/25/17 and 8/18/17 indicates in alarm; L12 <br /> dispenser 3/4 brine alarm since 8/20/17; L14 dispenser 7/8 brine alarm since 8/23/17, L18 vent annular space <br /> alarm since 6/19/17. <br /> 5) On the 9/7/17 DO report: L6 91 annular space alarm on 9/4/17, 9/5/17, and 9/6/17; L11 dispenser 1/2 brine <br /> alarm since 8/18/17, L12 dispenser 3/4 brine alarm since 8/20/17; L14 dispenser 7/8 brine alarm since 8/28/17; L18 <br /> vent annular space alarm since 8/18/17. <br /> 6) On the 10/9/17 DO report: L14 dispenser 7/8 brine alarm since 9/28/17; L11 dispenser 1/2 brine alarm since <br /> 8/18/17; L12 dispenser 3/4 brine alarm since 8/20/17; L18 vent annular space alarm since 6/19/17. <br /> 7) On the 11/16/17 DO report: L11 dispenser 1/2 brine alarm since 8/18/17; L12 dispenser 3/4 brine alarm since <br /> 8/20/17; L14 dispenser 7/8 brine alarm since 9/28/17; L15 87 annular space alarm sine 11/13/17; L18 vent annular <br /> space alarm since 6/19/17. <br /> 8) On the 12/4/17 DO report: L11 dispenser 1/2 brine alarm since 8/18/17; L12 dispenser 3/4 alarm since 8/20/17; <br /> L14 dispenser 7/8 alarm since 9/28/17; L15 87 STP sump annular alarm since 11/3/17; L18 vent annular alarm <br /> since 6/19/17. <br /> 9) On the 1/23/18 DO report: L11 dispenser 1/2 brine alarm since 8/18/17; L12 dispenser 3/4 alarm since 8/20/17; <br /> L14 dispenser 7/8 alarm since 9/28/17; L15 87 STP sump annular alarm since 11/3/17; L18 vent annular alarm <br /> since 6/19/17. <br /> 10) On the 2/9/18 DO report: L11 dispenser 1/2 brine alarm since 8/18/17; L12 dispenser 3/4 alarm since 1/25/18; <br /> L14 dispenser 7/8 alarm since 9/28/17; L15 87 STP sump annular alarm since 2/5/18; L16 91 STP annular space <br /> on 1/30/18; L18 vent annular alarm since 1/25/18. <br /> 11) On the 3/5/18 DO report: L12 dispenser 3/4 brine alarm since 3/5/18; L14 dispenser 7/8 brine alarm on 2/23/18 <br /> -2/27/18, and 3/5/18; <br /> 12) On the 4/3/18 DO report: L11 dispenser 1/2 brine alarm on 4/2/18; L12 dispenser 3/4 brine alarm on 3/5/18; <br /> L14 dispenser 7/8 brine alarm since 4/2/18; L18 vent annular space alarm since 2/26/18. <br /> During the monthly inspection, the designated operator shall review the alarm history for the previous month, check <br /> that each alarm was documented and responded to appropriately, and attach a copy of the alarm history with <br /> documentation taken in response to any alarms to the monthly report. Ensure that designated operators <br /> performing monthly inspections at this facility are including all of the required information on the reports. <br /> This is a Class II violation. <br /> FA0003831 PR0231760 SCO01 04/10/2018 <br /> EHD 23-01 Rev.10/31/2017 Page 5 of 8 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />