Laserfiche WebLink
SAN J O A Q! ,u I r, _nvironmental Health Department <br /> --C©U N T- Y - <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> WATERLOO FOODMART 4315 E WATERLOO RD, STOCKTON April 10, 2018 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 314 HSC 25290.1, 25290.2, 25291 Failed to have secondary containment or secondary containment not tight. <br /> Designated operator inspection reports from May 2017 through April 2017 indicate alarms and leaks from the <br /> interstitial spaces of each UDC and sumps. According to those reports, brine has been added on 6/28/17, 7/24/17, <br /> 8/25/17, 10/9/17, 11/16/17, 3/5/18, and 4/3/18. According to the work orders by Elite IV, brine was added on <br /> 1/25/18, and on that work order, it states"sensor positions are leaking too much to clear."On the work order dated <br /> 2/13/18, Elite IV stated "L18 Vent transition has a well known leak, and is pointless to keep refilling brine reservoir. <br /> Suggest site not waste brine."On the work order dated 6/20/17 by Elite IV, and L18 alarm was present, and <br /> according to the work order, "saw brine exiting from penetration boot."On the work order dated 7/12/17 by Elite IV, <br /> indicates vent sump, and UDC 1/2 both have low brine levels, and "1/2 UDC level would not stabilize, and Vent <br /> transition is leaking inside containment box."On the work order dated 6/13/17 by Elite IV, dispenser 1/2 brine levels <br /> were low, and they attempted to add 2 cups of brine. <br /> During the inspection, the service technician stated the vent electrical penetration was leaking brine, and no brine <br /> was observed in the reservoir, and brine was observed on the floor of the vent sump. In UDC 3/4, inadequate brine <br /> levels was found in the brine reservoir. Secondary containment shall be impervious to the liquid and vapor of the <br /> substance contained and constructed to prevent structural weakening as a result of contact with any hazardous <br /> substances released from the primary containment. Immediately contact a properly licensed, trained, and certified <br /> contractor to make repairs to the UST system under permit and inspection of the EHD. <br /> This is a Class II violation. <br /> 316 HSC 25290.1(c3), 25290.2(c3) Secondary containment not constructed to prevent water intrusion (after Jul 2003). <br /> According to a work order from Elite IV dated 3/31/18, water was found in the 87 STP sump, and the water was <br /> removed. According to the DO monthly report dated 11/16/17, water was found in the 91 STP sump. According to <br /> the DO monthly report dated 4/3/18, water was found in the 87 STP sump on 3/31/18 and removed. Secondary <br /> containment shall be constructed to prevent any water intrusion into the system by precipitation, infiltration, or <br /> surface runoff. Immediately contact a properly licensed, trained, and certified contractor to address the water <br /> intrusion into the 87, and 91 STP sump under permit and inspection of the EHD. <br /> This is a repeat violation, Class ll. <br /> Overall Inspection Comments: <br /> Upon arrival to inspection, the L18 vent annular and L12 dispenser 3/4 annular were in alarm. These alarms <br /> were not cleared at the end of the inspection. Inadequate levels of brine were observed in the reservoirs of the <br /> vent sump, and UDC 3/4. Monitoring system certification is incomplete. Vacuum communication was only <br /> verified on the vent sump, and could not be verified on the UDC's. Brine communication for the STP sumps and <br /> fill sumps were not completed during inspection, and has not been completed since the 4/10/17 inspection <br /> report. <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, within 30 days receipt of this report. <br /> Please be aware that as of January 1, 2014, facility operators are required to upload the following UST program <br /> FA0003831 PR0231760 SCO01 04/10/2018 <br /> EHD 23-01 Rev.10/31/2017 Page 7 of 8 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />