Laserfiche WebLink
^ <br />^ ' <br />TANKNOLO8Y - UNDERGROUND LEAK <br />DETECTION SYSTEM <br />- (V3.12) Page 15 <br />SHELL <br />HUU9203-0[910623-46733-08 - May 03, 1992/ O1:19 <br />�e--N C: ILJ_� <br />FEE f--- -r -F EF F-3 -r <br />E3 M M 0k F-* V <br />TEST DATE <br />: Mar 03, 1992 <br />START TIME <br />: 01:19:11 <br />CLIENT <br />SHELL <br />LOCATION NAME <br />: SHELL <br />LOCATION CODE <br />: 7524-2804 <br />TANK CONFIGURATION <br />: Tandem <br />TANK CONTENTS <br />: R/UNL <br />TANK NUMBER <br />03 <br />04 <br />TANK DIAMETER <br />: 94 <br />94 in <br />TANK CAPACITY <br />5000 <br />5000 G <br />TANK MANUFACTURER <br />: <br />TANK MATERIAL <br />: Steel <br />Steel <br />TANK REGISTRATION # <br />: <br />TANK DATE INSTALLED <br />INITIAL DIPPED FUEL LEVEL <br />: 80.00 <br />81.00 in <br />INITIAL DIPPED WATER LEVEL <br />: 0.00 <br />0.00 in <br />POST PUMPING WATER LEVEL <br />: 0.00 <br />0.00 in <br />X !NJ Fn:T E-: i��_ r --r-, U- E; 4-11— <br />TEST INITIAL INITIAL WATER LEVEL <br />: 0.00 <br />0,00 in <br />TEST FINAL WATER LEVEL <br />: 0.00 <br />0.00 in ' <br />WATER INGRESS <br />: 0.00 <br />0.00 in <br />BUBBLE SIGNATURES <br />: No <br />, No <br />VACU-TECT TEST RESULT <br />: Passed <br />Passed <br />COMMENTS: <br />CONCLUSION: BOTH R/UNL TANKS TESTED TIGHT. <br />' <br />L_ I FNJ EE -��--::!E�-� F---! EE E3 ILJ L--IF <br />TEST RATE TEST RATE <br />LINE PRESSURE OF LOSS RESULTPRESSURE OF JSS <br />#1 Passed 50 PSI 0.00 6PH <br />#2 <br />#3 <br />#4 <br />#5 <br />#6 <br />COMMENTS: <br />CONCLUSION: R/UWLEADED LINE TESTED TIGHT. <br />This test was conducted in 8CCOTdance with U.S. EPA Rule 40 CFR Parts 280 and 281. <br />HOU9203-IVE910623-467 K3 03 <br />0�B�W VACU-TECT(tm) Test Number <br />