Laserfiche WebLink
' L NO RE: -T-EE E3"F FO Ew E3 LJK - <br /> TEST RATE TEST RATE <br /> LINEPRESSURE -am LOSS- RESULT ...__ PRESSURE OF LOSS <br /> #1 Passed 50 PSI . Passed 0 00 8PH P d <br /> v 50 PSI 0 00 SPH <br /> #2 � ^ <br /> #3 <br /> #4 <br /> #5 <br /> #6 ' <br /> COMMENTS: <br /> ' <br /> CONCLUSION: LINES TESTED TIGHT ' <br /> This tet was conducted in accordance with U.S. BA Rule 40 CFR Parts 280 and 281. <br /> "^^^ `""^^=E VACU-TECT(tm) Test Number <br /> TANKNOLOGY - UNDERGROUND LEAK DETECTION SYSTEM - (V3. 12) Page 7 <br /> WILLIAMS NORBY <br /> HOU903-IVE9OV748-175043 - Mar 04/ l99l, 2148 ' <br /> -�df-� ID E=7-T_n-- TE L_ <br /> Tank configuration : Tandem <br /> Tank contents : UNLEADED/UNLEADED <br /> Tank number : 03 04 <br /> Tank manufacturer : <br /> Tank registration # : <br /> Date tank was installed <br /> Tank capacity :' 5000 5000 8 <br /> Tank diameter : 95 95 in <br /> Tank material : Steel Steel <br /> ' <br /> Fill tube insert present : Yes Yes <br /> Insert removed for test : Yes Yes <br /> Vent pipe fitting : 2. 00 2. 00 in <br /> Fill pipe fitting : 4. 00 4. 00 in <br /> Dipped fuel level : 59. 00 80. 00 in <br />^ Dipped water level : 0. 00 0. 00 in <br /> Post pumping water level : 0. 00 0. 00 in <br />