Z <br /> ® � MI EZ TM ® P.O. BOIX 8042 <br /> 27NVIRONMENTAL SYSTEMS, INC. <br /> BAKERSFIELD, CA 93380 <br /> (805)393-2212 <br /> INVOICE NUMBER I d 4 <br /> AES HYDROSTATIC PRODUCT LINE TEST WORK SHEET <br /> TEST PRODUCT START END START END TEST VOL. <br /> NO. TIME TIME VOL. (ml) VOL. (ml) DIFF. (ml) <br /> � /6 ;u() / 2 (;� / Z <br /> Divide the volume differential by the test time (15 minutes) and <br /> multiple by 0.0158311, which will convert the volume differential <br /> from milliliters per minute to gallons per hour. <br /> The conversion constant is found by: <br /> (60 rain/hr)/ (3790 ml/gal) = 0. 0158311 (min/hr) (gal/ml) <br /> The conversion constant causes the milliliters and minutes to <br /> cancel out. <br /> Ex. If the level dropped 3ml in 15 minutes then: <br /> 3/15 ml./min. X 0. 0158311 (min/hr) (gal/ml) = 0. 003 gal/hr. <br /> RESULTS OF THIS WORK SHEET TO BE COMPLIED ON A.E.S. RESULTS <br /> SHEET. <br />