Laserfiche WebLink
f-Js ACITY 10,000 g. PRECISION UNDERGROUND TANK TESTING RESULT Patent Pending <br /> { T. * 787 PAGE 1, SHORT FORM - Copyright 1985 <br /> :NK # 3 Reg. 10K <br /> TEST DATE: 02/18/1988 NDB TECHNOLOGY, INC. PROPRIETARY <br /> 1. Owner of storage tanks DESERT PETROLEUM <br /> Company Representative John Rutherford <br /> Title Director Environmental Affairs <br /> 2. Mailing address of owner P. 0. Box 1601 <br /> Oxnard, California 93032 <br /> 3. Phone of owner (806) 644--6784 <br /> 4. Station Number 787 <br /> 5. Location and address of GASCO - 950 W. 11th <br /> the tanks Tracy, California 95304 <br /> Phone number (209) 826-9910 <br /> 6. Regulatory Agency <br /> County of San Joaquin <br /> 7. Tank Designrtion or ID 3 Reg. 10K <br /> 8. Date each tank was tested 02/18/1988 <br /> 9. The name of the test method VPLT COMPUTERIZED TANK TESTING SYSTEM <br /> Business ,name of tank <br /> testing company WESTERN AMERICA TANK TESTING, INC. <br /> Mailing address of .tank 3131 FAIRHAVEN DRIVE <br /> testing company BAKERSFIELD, CA 93308 <br /> Person conducting test Brad Waggener (TEST TECHNICIAN) <br /> r j and completing report <br /> (Signed) . <br /> t <br /> 11. Station Operator or John Rutherford <br /> manager <br /> 12. Phone number (209) 826-9910 <br /> 13. Owner name and DESERT PETROLEUM <br /> title <br /> 14. Capacity of the tank 10,000 gallons <br /> F 15. Present or past contents Regular <br /> 16. Tank construction material Steel <br /> 117. Testing fluid Regular <br /> 18. (a) THE UNDERGROUND STORAGE TANK SYSTEM CERTIFIED TIGHT AT PRODUCT <br /> HEI.GHT: EQUAL TO THE GRADE LEVEL Yes <br /> (b) Allowable leak resolution of instrumentation or allowable change <br /> per California Administrative Code Title 23 Waters, Chapter 3 <br /> Water_Resources.--._Co.n_t ro.l_-B.oar.d-_.Subchap.t er--l6-Under-ground--Storage------ <br /> Regulations, Part 2643 (b) , Page 4.14; 0.05 gallons per hour. <br /> * * (c) MEASURED HOURLY CHANGE: LOSS (+) OR GAIN. (-) GALLONS OR <br /> NUMERICAL LEAK RATE IS: +0.044 Gallons Per Hour,, <br /> . ------- -- - ----- �-------- - ----__-_-- ------ ------- <br /> This measurement is within-the legal limits as defined in (b) <br /> NDE TECHNOLOGY, INC. PROPRIETARY <br /> oA7nnrrrau <br />