Laserfiche WebLink
May 8, 1996 LAB No: STK 632273-1 <br /> Luhdorff & Scalmanini , Consulting Eng. Sampled May 2, 1996 <br /> Sample Site: Quarterly Water Sampling <br /> Description: Browns New Sample type: Drinking Water <br /> General Mineral Analytical Results <br /> CONSTITUENT METHOD UNITS DLR RESULTS MCL <br /> Aggressiveness Index Calc. --- 0. 1 12.0 <br /> Langlier Index (Corrosivity) 0.1 0.1 <br /> pH 150.1 --- 7.4 <br /> E.C. 120.1 umbos/cm 1 840 1600 (b) <br /> TDS (Residue-at 180°C) 160.1 mg/L 40 510 1000 (b) <br /> TDS (by Summation) Calc. mg/L 1 680 <br /> MBAS 425.1 mg/L 0.05 ND 0.5 <br /> Boron (B) 200.7 mg/L 0.1 1.1 <br /> Copper (Cu) 200.7 ug/L 30 ND 1000 <br /> Iron (Fe) 200.7 ug/L 30 1900 300 ,1 <br /> Manganese (Mn) 200.7 ug/L 30 ND 50 <br /> Zinc (Zn) 200.7 ug/L 30 ND 5000 <br /> ND = Not Detected greater than or equal to the DLR. DLR = Detection Limit for Reporting purposes <br /> MCL = Maximum Contaminant Level (California Health & Safety Code, Title 22) <br /> ug/L = Micrograms Per Liter (ppb) mg/L = Milligrams Per Liter (ppm) <br /> (b) Upper Limit, Mineralization - Secondary Drinking water Standards. <br /> FGL VIRONMEN <br /> r <br /> Kurt Wilkins n, B. . <br /> Laboratory irector <br /> KW:jgc <br />