Laserfiche WebLink
May 8, 1996 LAB No: STK 632273--6 <br /> Luhdorff & Scalmanini , Consulting Eng. Sampled : May 2, 1996 <br /> Sample Site: Quarterly Water Sampling <br /> Description: Browns #1 Sample type: Drinking Water <br /> General Mineral Analytical Results. <br /> CONSTITUENT METHOD UNITS DLR RESULTS MCI. <br /> Aggressiveness Index Caic. --- 0.1 11.9 <br /> Langlier Index (Corrosivity) 0.1 0.0 <br /> pH 150.1 --- 7.3 <br /> E.C. 120.1 umhos/cm 1 880 1600 (b) <br /> TDS (Residue.-at 180°C) 160.1 mg/L 40 540 1000 (b) 4 <br /> TDS (by Summation) Calc. mg/L 1 704 <br /> MEAS 425.1 mg/L 0.05 ND 0.5 <br /> Boron (B) 200.7 mg/L 0.1 1.1 <br /> .Copper (Cu) 200.7 ug/L 30 NO 1000 <br /> Iron (Fe) 200.7 ug/L 30 5800 300 0 <br /> Manganese (Mn) 200.7 ug/L 30 190 50 <br /> Zinc (Zn) 200.7 ug/L 30 580 5000 <br /> ND = Not Detected greater than or equal to the DLR. DLR = Detection Limit for Reporting purposes <br /> MCL = Maximum Contaminant Level (California Health & Safety Code, Title 22) <br /> ug/L = Micrograms Per Liter (ppb) mg/L = Milligrams Per Liter (ppm) <br /> (b) Upper limit, Mineralization - Secondary Drinking Water Standards. <br /> FGL VIRONMEN L <br /> c U <br /> Kurt Wilkinso , B. <br /> Laboratory D rector <br /> KW:jgc <br />