Laserfiche WebLink
0 <br /> October 24, 1996 LAB No: STK 635407-3 <br /> Luhdorff & Scalmanini , Consulting Eng. Sampled October 16, 1996 <br /> Sample Site: Quarterly Water Sampling q <br /> Description: Koster Sample type: Drinking Water <br /> General Mineral Analytical Results <br /> CONSTITUENT METHOD UNITS DLR RESULTS MCL <br /> Aggressiveness Index Calc. --- 0.1 11 .8 <br /> Langlier Index (Corrosivity) 0.1 -0.1 <br /> pH 150.1 --- 7.4 <br /> E.C. 120.1 umhos/cm 1 840 1600 (b) <br /> TDS (Residue-=at 180°C) 160.1 mg/L 40 500 1000 (b) <br /> TDS (by Summation) Cale. mg/L 1 601 <br /> MBAS 425.1 mg/L 0.05 ND 0.5 <br /> Boron (B) 200.7 mg/L 0.1 ND <br /> Copper (Cu) 200.7 ug/L 30 ND 1000 <br /> Iron (Fe) 200.7 ug/L 30 100 300 <br /> Manganese (Mn) 200.7 ug/L 30 ND 50 <br /> Zinc (Zn) 200.7 ug/L 30 ND 5000 <br /> RD = Not Detected greater than or equal to the DER. DLR = Detection Limit for Reporting purposes <br /> MCL = Maximum Contaminant Level (California Health & Safety Code, Title 22) <br /> ug/L = Micrograms Per Liter (ppb) mg/L = Mitligrams Per Liter (ppm) <br /> (b) Upper limit, Mineralization - secondary Drinking Water Standards. <br /> FGL ENVIRONMENTAL <br /> Charles Johnson, B.S. <br /> Laboratory Manager <br /> CJ:jgc <br />