Laserfiche WebLink
i <br /> I <br />� November 6, 1997 <br /> LAS No: STK 736197-1 <br /> Luhdorff & Scaimanin, Consulting Enginee Sampled October 16, 1997 <br /> Sample Site: Quarterly Water Sampling <br /> Description: Faulkner Sample type: Drinking Water ILA <br /> i <br /> General Mineral Analytical Results <br /> CONSTITUENT METHOD UNITS DLR RESULTS MCL <br /> Aggressiveness Index Calc. --- 0. 1 12. 1 <br /> j Langlier Index (Corrosivity) 0. 1 0.3 <br /> i pH 4500-H B --- 7.5 <br /> E.C. 2510B umhos/cm 1 980 1600 (b) <br /> TQS (Residue at 180°C) 2540C mg/L 40 610 . 1000 (b) <br /> TOS (by Summation) Calc. mg/L 1 686 <br /> MBAS 5540C mg/L 0.05 ND 0.5 <br /> Boron (B) 200.7 mg/L 0.1 0.4 <br /> Copper (Cu) 200.7 ug/L 50 ND 1000 <br /> Iron (Fe) 200.7 ug/L 50 ND 300 <br /> Manganese (Mn) 200.7 ug/L 30 ND 50 <br /> Zinc (Zn) 200.7 ug/L 50 ND 5000 <br /> ND = Not Detected greater than or equal to the DLR. DLR = Detection Limit for Reporting purposes <br /> MCL = Maximum contaminant Level (California Health & Safety Code, Title 22) <br /> ug/L = Micrograms Per Liter (ppb) mg/L = Milligrams Per Liter (ppm) <br /> (b) Upper limit, Mineralization - secondary Drinking Mater Standards. <br /> FGL ENVIRONMENTAL <br /> r <br /> 0 <br /> n CharlesJ nson, B.S. <br /> Laborat0 Manager <br /> CJ:jgc <br /> I� <br /> i <br />