Laserfiche WebLink
I <br /> I <br /> I <br /> November 9, 1995 LAB No: STK 534772-5 <br /> Luhdorff & Scalmanini , Consulting Eng. Sampled ; October 11 , 1995 <br /> Sample- Site: Quarterly Water Sampling <br /> Description: Hall Sample type: Drinking Water <br /> General Mineral Analytical Results <br /> CONSTITUENT METHOD UNITS DLR RESULTS MCL <br /> Aggressiveness Index Calc. --- 0.1 12.1 <br /> Langlier Index (Corrosivity) <br /> 0. 1 0.3 <br /> pH 150.1. ---- 7.4 <br /> E•C• 120.1 umbos/cm 1 1000 1600 <br /> t TDS (Residue at 180°C) 160.1 mg/L 40 620 1000 (b) <br /> I TDS (by Summation) Calc. mg/L 1 770 <br />[ MBAS 425.1 mg/L 0.05 ND 0.5 <br /> Boron (B) 200.7 mg/L 0.1 0.5 <br /> Copper (Cu) 200.7 ug/L 50 ND 1000 <br /> Iron (Fe) 200.7 ug/L 50 ND 300 <br /> Manganese (Mn) 200. 7 ug/L 30 ND 50 <br /> Zinc (Zn) 200. 7 ug/L 50 NO 5000 <br /> ND = Not Detected greater than or equal to the DLR. DLR = Detection Limit for Reporting purposes <br /> MCL = Maximum Contaminant Level (California Health & Safety Code, Title 22) <br /> ug/L = Micrograms Per Liter (ppb) mg/L = Milligrams Per Liter (ppm) <br /> (b) tipper limit, Mineralization Secondary Drinking Water Standards, <br /> FGL ENVIRONMENTAL <br /> Kurt Wilkinson, B.S. <br /> Laboratory Director <br /> j KW:jgc i <br /> r � <br /> Anion/cation balance not within acceptance limits . All anion/cation <br /> analyses confirmed. Constituents not analyzed may be affecting balance. <br /> I <br /> 1 <br /> J1 <br />�� I <br />