Laserfiche WebLink
f <br /> f <br /> November 9, 1995 LAB No: STK 534772-4 <br /> Luhdorff & Scalmanini , Consulting Eng. Sampled October 11 , 1995 <br /> Sample Site: Quarterly Water Sampling <br /> Description: Faulkner Sample type: DrinkingWater <br /> General Mineral Analytical Results <br /> CONSTITUENT METHOD UNITS DLR . RESULTS MCL <br /> Aggressiveness Index Calc. --- 0.1 12.4 <br /> Langlier Index (Corrosivity) 0. 1 0.6 <br /> pH 150.1 --- 7.7 <br /> E .C. 120.1 umhos/cm 1 1000 1600 (b) <br /> TDS (Residue at 180°C) 160. 1 mg/L 40 600 1000 (b) <br /> TDS (by Summation) Calc. mg/L 1 759 <br /> MBAS 425.1 mg/L 0.05 ND 0.5 <br /> Boron (8) 200.7 mg/L 0. 1 0.4 <br /> Copper (Cu) 200. 7 ug/L 50 ND 1000 <br /> Iron (Fe) 200. 7 ug/L 50 ND 300 <br /> Manganese (Mn) 200. 7 ug/L 30 ND 50 <br /> Zinc (Zn) 200.7 ug/L 50 ND 5000 <br /> ND = Not Detected greater than or equal to the DLR. DLR = Detection Limit for Reporting purposes <br /> MCL = Maximum Contaminant Level (California Health & Safety Code, Title 22) <br /> ug/L = Micrograms Per Liter (ppb) mg/L = Milligrams Per Liter (ppm) <br /> (b) Upper limit, Mineralization - Secondary Drinking Water Standards. , <br /> FGL ENVIRONMENTAL <br /> Kurt Wilkinson, B.S. <br /> Laboratory Director <br /> KW:jgc <br /> Anion/cation balance not within acceptance limits . All anion/cation <br /> analyses confirmed. Constituents not analyzed may be affecting balance. <br /> 4 I <br /> I � ' <br />