Laserfiche WebLink
I <br /> i <br /> November 9, 1995 LAB No: STK 534772-1 <br /> I <br /> Luhdorff & Scalmanini , Consulting Eng. Sampled October 11 , 1995 <br /> Sample Site: Quarterly Water Sampling <br /> Description: Browns New Sample type: Drinking Water, <br /> General Mineral Analytical Results <br /> CONSTITUENT METHOD UNITS DLR RESULTS MCL <br /> Aggressiveness Index Calc. --- 0.1 12. 1 <br /> Langlier Index (Corrosivity) 0.1 0.2 <br /> pH 150.1 -- <br /> 7.5 <br /> E.C. 120.1 umhos/cm 1 830 1600 (b) <br /> TDS (Residue at 180°C) 160.1 mg/L 40 550 1000 (b) <br /> TITS (by Summation) Calc. mg/L 1 694 <br /> MBAS 425. 1 mg/L 0.05 NO 0.5 <br /> Boron (B) 200.7 mg/L 0.1 1.0 <br /> Copper (Cu) 200. 7 ug/L 50 NO 1000 <br /> Iron (Fe) 200. 7 ug/L 50 NO 300 <br /> Manganese (Mn) 200.7 ug/L 30 NO 50 <br /> Zinc (Zn) 200.7 ug/L 50 NO 5000 <br /> NU = Not Detected greater than or equal to the DLR, DLR = Detection Limit for Reporting purposes <br /> MCL = Maximum contaminant Level (California Health & Safety Code, Title 22) <br /> f ug/L = Micrograms Per Liter (ppb) mg/L = Milligrams Per Liter (ppm) <br /> (b) Upper limit, Mineralization - Secondary Drinking Water Standards. ' <br /> i <br /> I <br /> FGL ENVIRONMENTAL <br /> Kurt Wilkinson, B.S. I <br /> Laboratory Director <br /> KW: jgc <br /> I <br /> Anion/cation balance not within acceptance limits . All anion/cation <br /> analyses confirmed. Constituents not analyzed may be affecting balance. <br />