Laserfiche WebLink
i 0 <br /> .i <br /> February 5, 1996 LAB No: STK 630171-5 <br /> Luhdorff & Scalmanini , Consulting Eng. Sampled January 11 , 1996 <br /> f " Sample Site: Quarterly Water Sampling <br /> Description: Hall Sample type: Drinking Water <br /> is General Mineral Analytical Results <br /> 0 <br /> CONSTITUENT METHOD UNITS DLR RESULTS MCL : <br /> �€ <br /> Aggressiveness Index Calc. -- 0.1 12. 1 <br /> Langlier Index (Corrosivity) 0.1 0.3 <br /> pH 150.1 7.4 <br /> E.C. 120.1 umhos/cm 1 1000 1600 (b) <br /> 4 TOS (Residue at 180°C) 160.1 mg/L 40 610 1000 (b) <br /> TDS (by Summation) Calc. mg/L 1 781 <br /> MBAS 425. 1 mg/L 0.05 NO 0.5 <br /> # Boron (8) 200.7 mg/L 0. 1 0.5 <br /> Copper (Cu) 200. 7 ug/L 50 NO 1000 <br /> Iron (Fe) 200.7 ug/L 50 ND 300 <br /> '. Manganese (Mn) 200.7 ug/L 30 ND 50 <br /> Zinc (Zn) 200.7 ug/L 50 ND 5000 <br /> p0 ND = Not Detected greater than or eguaL to the DLR. DLR = Detection Limit for Reporting purposes <br /> MCL = Maximum contaminant Leve( (California Health $ Safety Code, Title 22) <br /> ug/L = Micrograms Per Liter (ppb) mg/L = Milligrams Per Liter (ppm) <br /> (b) Upper limit, Mineralization secondary Drinking hater Standards. <br /> :t <br /> i <br /> j FGL ENVIRONMENTAL <br /> Kurt Wilkinson, B.S- <br /> i <br /> Laboratory Director <br /> KW:jgc <br /> Note: Anion/cation balance not within acceptance criteria. All anion/cation <br /> analyses confirmed. Constituents not analyzed may be. affecting balance. <br /> I ' <br /> .i <br /> .i - <br />