F 2 <br /> li <br /> I <br /> February 5, 1996 LAB No: STK 630171-6 <br /> Luhdorff & Scalmanini , Consulting Eng_ Sampled January 11 , 1996 <br /> j Sample Site: Quarterly Water Sampling <br /> Description: Browns #1 Sample type: Drinking Water <br /> General Mineral Analytical Results <br /> i <br /> like' ' CONSTITUENT METHOD UNITS DLR RESULTS MCL <br /> Aggressiveness Index Calc. --- 0.1 12.2 <br /> Langlier Index (Corrosivity) 0.1 0.4 <br /> pH 150. 1 --- 7.6 <br /> E .C. 120. 1 umhos/cm 1 870 1600 (b) <br /> TDS (Residue at 180°C) 160. 1 mg/L 40 580 1000 (b) <br /> TDS (by Summation) Calc. mg/L 1 711 <br /> MEAS 425.1 mg/L 0.05 ND 0.5 <br /> Boron (B) 200.7 mg/L 0.1 1 .1 <br /> Copper (Cu) 200.7 ug/L 50 ND 1000 <br /> Iron (Fe) 200. 7 ug/L 50 9300 300 <br /> Manganese (Mn) 200. 7 ug/L 30 130 50 <br /> Zinc (Zn) 200. 7 ug/L 50 190 5000 <br /> 4 ND = Not Detected greater than or equal to the DLR. DLR = Detection Limit for Reporting purposes <br /> II MCL = Maximum Contaminant Level (California Health 8 Safety Code, Title 22) <br /> ug/L = Micrograms Per Liter (ppb) mg/L = Milligrams Per Liter (ppm) <br /> i (b) Upper limit, Mineralization Secondary Drinking Water Standards. <br /> FGL ENVIRONMENTAL <br /> n <br /> y <br /> Kurt Wilkinson, B.S_ <br /> Laboratory Director <br /> KW:jgc <br /> Note: Anion/cation balance not within acceptance criteria . All anion/cation <br /> analyses confirmed. Constituents not analyzed may be affecting balance. <br /> 1 <br /> i <br /> l <br />