May 8, 1996 LAB No: STK 632273-1 <br /> Luhdorff & Scalmanini , Consulting .Eng P Y Sampled May 2 1996 <br /> Sample Site: Quarterly Water Sampling <br /> i Description: Browns New Sample type: Drinking Water <br /> General Mineral Analytical Results <br /> CONSTITUENT METHOD UNITS DLR RESULTS MCL <br /> Aggressiveness Index Calc. --- 0. 1 12.0 <br /> Langlier Index (Corrosivity) 0. 1 0. 1 <br /> pH 150. 1 --- 7.4 <br /> E.C. 120. 1 umhos/cm 1 . 840 1600 (b) <br /> TDS (Residue at 180°C) 160.1 mg/L 40 510 1000 (b) <br /> TDS (by Summation) Calc. mg/L 1 680 <br /> MBAS 425. 1 mg/L 0.05 ND 0.5 <br /> Boron (B) 200.7 mg/L 0. 1 1 .1 <br /> Copper (Cu) 200. 7 ug/L 30 NO 1000 <br /> Iron (Fe) 200.7 ug/L 30 1900 300 <br /> Manganese (Mn) 200.7 ug/L 30 ND 50 <br /> Zinc (Zn) 200.7 ug/L 30 NO 5000 <br /> ND = Not Detected greater than or equal to the DLR. DLR = Detection Limit for Reporting purposes <br /> MCL = Maximum Contaminant Level (California Health & Safety code, Title 22) <br /> ug/L = Micrograms Per Liter (ppb) ae/L = Milligrams Per Liter (ppm) <br /> (b) Upper limit, Mineralization Secondary Drinking Water Standards. <br /> FGL VIReNMEN <br /> Kurt Wilkins n, B. <br /> Laboratory irector <br /> KW:jgc <br /> n <br /> 4 <br />