Laserfiche WebLink
i <br /> May 8, 1996 LAB No: STK 632273-6 <br /> L-uhdorff & Scalmanini , Consulting Eng. Sampled May 2, 1996 <br /> Sample Site: Quarterly Water Sampling <br /> Description: Browns #1 Sample type: Drinking Water <br /> a <br /> General Mineral Analytical Results <br /> CONSTITUENT METHOD UNITS DLR RESULTS MCL <br /> Aggressiveness Index Calc. --- 0. 1 11 .9 <br /> Langlier Index (Corrosivity) O. J. 0.0 <br /> pH 150. 1 --- 7.3 <br /> E.C. 120. 1 umhos/cm 1 880 1600 (b) <br /> TDS (Residue at 180°C) 160. 1 mg/L 40 540 1000 (b) <br /> TDS (by Summation) Calc. mg/L 1 704 <br /> MBAS 425. 1 mg/L 0.05 NO 0.5 <br /> Boron (B) 200.7 mg/L 0.1 1 . 1 <br /> Copper (Cu) 200.7 ug/L 30 NO 1000 <br /> Iron (Fe) 200. 7 ug/L. 30 5800 300 <br /> Manganese (Mn) 200.7 ug/L. 30 190 50 <br /> Zinc (Zn) 200.7 ug/L 30 580 5000 <br /> ND = Not Detected greater than or equal to the DLR. DLR = Detection Limit for Reporting purposes <br /> MCL = Maximum Contaminant Levet (California Health & Safety Code, Title 22) <br /> ug/L = Micrograms Per Liter (ppb) mg/L = Milligrams Per Liter (ppm) <br /> (b) Upper limit, Mineralization Secondary Drinking Water Standards, <br /> FGL E VIRONMEN L <br /> n l <br /> Kurt Wilkinso B. <br /> Laboratory D rector <br /> KW:jgc <br /> r - <br /> r <br />