Laserfiche WebLink
Pump Selection for a Pressurized System <br /> Input Parameters - <br /> Orifice Size 5132 inches <br /> Residual Head at Last Orifice 5.00 feet 160 Effluent Pumps OrenCO S"ten7S <br /> Orifice Spacing 4.0 feet P5015 P50 Series Incorporated <br /> Number of Laterals per Cell 2 1/2 hp to 1-1/2 h <br /> Lateral Length 88.0 feet <br /> Lateral Line Size 1.50 inches 140 814AIRWAYAVENUE <br /> Lateral Pipe Class/Schedule 40 SUTHERUN,OREGON <br /> Distributing Valve Model None <br /> Manifold Length 3.3 feet -- 97479 <br /> Manifold Line Size 1.50 inches 120 P5010 <br /> Manifold Pipe Class/Schedule 40 - <br /> Lift to Manifold 5.0 feet TOLL FREE: <br /> Transport Length 110.0 feet v (800)348-9843 <br /> Transport Line Size 1.50 inches 100 <br /> Transport Pipe Class/Schedule 40 p <br /> Discharge Assembly Size 1.50 inches F_ P5007 TELEPHONE: <br /> Flow Meter 1.5 inches m (541)4594W <br /> 'Add-on'Friction Losses 10.0 feet a) 80 <br /> U <br /> Calculations m - FACSIMILE: <br /> Minimum Flow Rate per Orifice 0.68 gpm r <br /> Number of Orifices per Zone 46 0 P5005 15411459-2984 <br /> Total Actual Flow Rate 31.5 gpm <br /> m 60 <br /> Number of Lines per Zone 2 ~ <br /> Flow Differential 1st and Last Orifice 4.7 % wwmorenco.com <br /> Lift to Manifold 5.0 feet - C <br /> Residual Head at Last Orifice 5.00 feet 40 <br /> Head Loss in Laterals 0.5 feet �- <br /> Head Loss Through Distributing Valve 0.0 feet <br /> Head Loss in Manifold 0.1 feet <br /> Head Loss in Transport Pipe 6.4 feet 20 <br /> Head Loss Through Discharge 3.0 feet <br /> Head Loss Through Flow Meter 2.7 feet <br /> 'Add-on'Friction Losses 10.0 feet <br /> 0 <br /> Total Flow Rate 31.5 gpm 0 10 20 30 40 50 60 70 <br /> TDH 32.6 feet <br /> Net Discharge, gpm <br />