Laserfiche WebLink
6. <br /> October 03, 2006 Lab ID : STK638127 <br /> Neil Anderson & Associates Customer : 3-9574 <br /> 6. <br /> Quality Control - Organic <br /> Constituent Method Date/ID Type Units Cone. QC Data DQO Note <br /> DBCP 504.1 09/27/2006:A203 Blank ug/L ND <0.01 <br /> LCS ug/L 0.2941 116% 70-130 <br /> .. BS ug/L. 0.2941 117% 70-130 <br /> BSD ug/L 0.2941 115% 70-130 <br /> BSRPD ug/L 1.6% 530 <br /> ` 504.1 09/27/2006:A 00-CCV ug/L 5.000 116% 70-130 <br /> 01-CCV ug/L 5.000 114% 70-130 <br /> 1,3-Dibromopropane-Surrogate 504.1 09/27/2006:A203 Blank ug/L 0.5882 123% 70-130 <br /> LCS ug/L 0.5882 118% 70-130 <br /> .. BS ug/L 0.5882 117% 70-130 <br /> BSD ug/L 0.5882 115% 70-130 <br /> 504.1 09/27/2006:A 00-CCV ug/L 9.975 118% 70-130 <br /> u. 01-CCV ug/L 9.975 114% 70-130 <br /> Definitions <br /> Blank Method Blank - Prepared to verify that the preparation process is not contributing contamination to the samples. <br /> LCS Laboratory Control Standard/Sample - Prepared to verify that the preparation process is not affecting analyte <br /> V recovery. <br /> BS/BSD Blank Spikes - A blank is spiked with a known amount of analyte. It is prepared to verify that the preparation <br /> process is not affecting analyte recovery. <br /> L ICB Initial Calibration Blank - Analyzed to verify the instrument baseline is within criteria. <br /> ICV Initial Calibration Verification - Analyzed to verify the instrument calibration is within criteria. <br /> CCB Continuing Calibration Blank - Analyzed to verify the instrument baseline is within criteria. <br /> CCV Continuing Calibration Verification - Analyzed to verify the instrument calibration is within criteria. <br /> ND Non-detect - Result was below the DQO listed for the analyte. <br /> DQO Data Quality Objective - This is the criteria against which the quality control data is compared. <br /> r <br /> r_ <br /> r <br /> r <br /> r_ <br /> STK638127: Quality Control Page 2 <br /> r_ <br />