Laserfiche WebLink
X8.22.4 y.,JUSTRIAL RELATIONS TITLE 8 <br /> (Register 7b-,-4o. 13-3-2375) <br /> (h) The total refrigeration load shall be computed as the sum of the <br /> following: <br /> (1) Load imposed by heat flow into the container caused by the <br /> temperature differential between design ambient temperature and <br /> storage temperature. <br /> (2) Load imposed by heat flow into the container caused by max- <br /> imum sun radiation. <br /> (3) Maximum load imposed by filling the container with ammonia <br /> warmer than the design storage temperature. <br /> More than one storage container may be handled by the same. <br /> refrigeration system. <br /> J(i) A minimum of two compressors shall be provided, either of which <br /> be of sufficient size to handle the loads listed in Section 514(h) (1) <br /> and (2). Where more than two compressors are provided, minimum <br /> standby equipment equal to the largest normally operating equipment <br /> shall be installed. Filling compressors may be used as standby equip- <br /> ment for holding compressors. <br /> Compressors shall be sized to operate with a suction pressure at least <br /> 10 percent below-the minimum setting of the safety valve(s) on the <br /> storage container and shall withstand a suction pressure at least equal <br /> to 120 percent of the designpressure of the container. <br /> 0) Each compressor shall have its individual driving unit. <br /> An emergency source of power of sufficient capacity to handle the <br /> loads listed in Section 514(h) (1) and (2) shall be provided unless facili- <br /> ties are available to safely dispose of vented vapors while the refrigera- <br /> tion system is not operating. <br /> (k) The refrigeration system shall be arranged with suitable controls <br /> togovern the compressor operation in accordance with the load as <br /> evidenced by thepressure in the container(s). <br /> An emergency alarm system shall be installed to function in the event <br /> the pressure in the container(s) rises to the maximum allowable operat- <br /> ing pressure. <br /> An emergency alarm and shutoff shall be located in the condenser <br /> system to respond to excess discharge pressure caused by failure of the <br /> cooling medium. <br /> All automatic controls shall be installed in a manner .to preclude <br /> operation of alternate compressors unless the controls will function <br /> with the alternate compressors. <br /> (1) An entrainment separator of suitable size and design pressure <br /> shall be installed in the compressor suction line of lubricated compres- <br /> sion. The separator shall be equipped with a drain and gaging device. <br /> An oil separator of suitable size shall be installed in the compressor <br /> discharge line. It shall be designed for at least 250 p.s.i. and shall be <br /> equipped with a gaging device and drain valve. <br /> (m) The condenser system may be cooled by air or water or both. <br /> The condenser shall be designed for at least 250 p.s.i. Provision shall be <br /> made for purging noncondensibles either manually or automatically. <br />