AMERICAN NATIONAL STANDARD K61.1-1951 <br /> 2.9.4 Pressure relief valves shall be so ar- remaining openings, the restricted opening or <br /> ranged that the possibility of tampering will be openings or those having the lowest flow shall be <br /> minimized.If the pressure setting adjustment is used to establish the flow rate marked on the <br /> external,the relief valves shall be provided with manifold nameplate. The marking shall be <br /> means for sealing the adjustment. similar to that required in 2.9.7 for individual <br /> 2.9.5 Shut-off valves shall not be installed valves. <br /> between the pressure relief valves and the con- 2.9.10 A hydrostatic relief valve or equivalent <br /> tainers or systems described in Sections 3, 6, 7 shall be installed in each section of piping <br /> and 8, except that as shut-off valve may used (including hose)in which liquid ammonia can be <br /> where the arrangement of this valve is such as isolated between shut-off valves so as to relieve <br /> always to afford required capacity flow through the pressure which could develop from the <br /> the relief valves. trapped liquid. If an equivalent pressure reliev- <br /> NOTE: The above exception is made to cover such cases as a ing device is used, the maximum accumulative <br /> threeway valve installed under two pressure relief valves, pressure possible within the.system shall not <br /> each of which has the required.rate of discharge and is so exceed the limits of the system. ' <br /> installed as to allow either of the pressure relief valves to be <br /> closed off.butdoes not allow both pressure relief valves to be 2.9.11 Discharge from pressure relief valves <br /> closed off at the same time.Another exception to this may be shall not terminate in or beneath any building. <br /> where two separate pressure relief valves are installed with <br /> individual shut-off valves.In this case,the two shutoff valve <br /> stems shall be mechanically interconnected in a manner 2.10 Safety <br /> which will allow full required flow of one pressure relief valve <br /> at all times.Still another exception is a pressure relief valve See CGA Pamphlet G-2 and TF1 Operational <br /> manifold which allowsone valve of two,three,fouror more to Safety Manual M-2 (See Appendix C for <br /> be closed off and the remaining valve or valves will provide availability). <br /> not less than the rate of discharge shown on the manifold aVay). <br /> nameplate. 2.10.1 Personnel required to handle ammonia <br /> shall be trained in safe operating practices and <br /> 2.9.6 Pressure relief valves shall have direct the proper action to take to emergencies. <br /> AW communication with the vapor space of the 2,10.2 If a leak occurs in a permanent storage <br /> +�1 container. installation, the <br /> personnel trained for and <br /> 2.9.7 Each pressure relief valve used with designated to act in such emergencies shall: <br /> systems described in Sections 3,4,6,7 and 8 shall (a) See that persons not required to deal with <br /> be plainly and permanently marked as follows: an emergency are evacuated from the contami- <br /> (a) With the letters"AA"or the symbol"NH;', nated area. <br /> (b) The pressure in pounds per square inch (b) Put on suitable respiratory protection. <br /> gage (psig) at which the valve is set to start-to- (c) Wear gauntlet type plastic or rubber gloves, <br /> discharge. plastic or rubber suits and protective boots in <br /> (c) The rate of discharge of the valve in cubic heavily contaminated areas. <br /> feet per minute of air at 60 F (15.6 C) and (d) Shut-off the appropriate valves. <br /> atmospheric pressure. (e) Notify state or federal governmental regu- <br /> (d) The manufacturer's name and catalog latory authorities as may be appropriate. <br /> number. 2.10.3 All permanent storage installations <br /> For example, a pressure relief valve marked shall have on hand,as a minimum,the followin <br /> AA-250-4200 (air)would mean that this valve is g <br /> suitable for use on an anhydrous ammonia equipment for emergency and rescue purposes: <br /> container; that it is set to start-to-discharge at '(a) One full face gas mask with one industrial <br /> 250 psig(1720 kPa);and that its rate of discharge size ammonia canister and at least one spare <br /> (see Sections 2.9.1, 2.9.2, and 2.9.3) is 4200 ammonia canister in a readily accessible location. <br /> cubic feet(118.9 ms) per minute of air. Positive pressure self-contained breathing appa- <br /> ratus must be used in ammonia contaminated <br /> 2.9.8 The flow capacity of the pressure relief atmospheres that are immediately dangerous to <br /> valve shall not be restricted by any connection to life or health. Gas masks and self contained <br /> it on either the upstream or downstream side. breathing apparatus must be approved by <br /> 2.9.9 The manufacturer or suppplier of apres- NIOSH/MSHAunder provisions of 30 CFR Part <br /> sure relief valve manifold shall Publish complete II. <br /> data showing the flow rating through the com- !An ammonia gas mask willprovide effective respiratory <br /> bined assembly of the manifold with pressure protection in concentrations of ammonia in air that are not <br /> relief valves installed.The manifold flow rating immediately dangerous to lifeor health(2500 ppm or less)for <br /> short periods of time. A gas mask is not recommended for <br /> f shall be determined by testing the manifold with respiratory protection in concentrations exceeding this <br /> all but one valve discharging. If one or more amount Faceaiece fitting shalt be used to determine the <br /> openings have restrictions not present in the ability of each individual gas mask wearer to obtain a <br /> 13 <br />