r AMERICAN NATIONAL STANDARD K61.1-1981 <br /> f <br /> be installed. Compressors required for 4.9.1.3 by air or water or bath. The condenser shall be <br /> may be used as standby equipment for com- designed for at least 250 psig (1720 kPa). Pro- <br /> pressors required in 4.9.1.1 and 4.9.1.2: vision shall be made for purging non-condensibles <br /> 4.9.3.2 Compressors shall be sized to operate either manually or automatically. <br /> with.a suction pressure at least 10% below the 4.9.8 Receiver and Liquid Drain <br /> minimum setting of the pressure relief valve(s) 4.9.8.1 A receiver shall be provided which is <br /> on the storage tank and shall withstand a suction equipped with cc automatic float valve to dis- <br /> pressure least equal 120,0Nof the design charge the liquid ammonia to storage or with a <br /> pressure off the tank. Discharge pressure will be <br /> governed by condensing conditions. high pressure liquid drain trap of suitable <br /> capacity. The receiver shall be designed for at <br /> 4.9.4 Compressor Drives least 250 psig(1720 kPa)operating pressure and <br /> be equipped with the necessary connections, <br /> 4.9.4.1 Each compressor shall have its pressure relief valves and gaging device. <br /> individual driving unit. 4.9.9 Insulation <br /> 4.9.4.2 Any standard drive consistent with 4.9.9.1 Refrigerated containers and pipe <br /> good design maybe used. lines which are insulated shall be covered with a <br /> 4.9.4.3 An emergency source of power of material of suitable quality and thickness for the <br /> sufficient capacity to handle the loads listed in temperatures encountered. Insulation shall be <br /> paragraphs 4.9.1.1 and 4.9.1.2 shall be provided, suitably supported and protected against the <br /> unless facilities are provided to safely dispose of weather. Weatherproofing shall be of a type <br /> vented vapors while the refrigeration system is which will not support flame propagation. <br /> not operating. <br /> 4.9.5 Automatic Control Equipment 4.10 Safety Equipment <br /> 4.9.5.1 The refrigeration system shall be 4.10.1 All refrigerated storage plants shall <br /> arranged with suitable controls to govern the have on hand the minimum safety equipment <br /> C ♦ compressor operation in accordance with the required under paragraph 2.10.3. <br /> load as evidenced by the pressure in the <br /> container(s). 5. SYSTEMS UTILIZING PORTABLE DOT <br /> CONTAINERS AND CYLINDERS <br /> 4.9.5.2 An emergency alarm system shall be <br /> installed to function in the event the pressure in This section applies specifically to systems <br /> the container(s) rises to the maximum or falls to Utilizing cylinders, portable tanks (DOT-51), or <br /> the minimum allowable operating pressure. "ton containers" (DOT-106A, DOT-110A), con- <br /> structed in accordance with Department of Trans- <br /> 4.9.5.3 An emergency- alarm and shut-off portation Specifications. ALl Basic Rules of <br /> shall be located in the condenser system to Section 2 apply to this section, unless otherwise <br /> respond to excess discharge pressure caused by noted. <br /> failure of the cooling medium. <br /> 4.9.5.4 All automatic controls shall be 5.1 Containers & Cylinders <br /> installed in a manner to preclude operation of 5.1.1 Containers and cylinders shall comply <br /> alternate compressors unless the controls will with current DOT specifications and shall be <br /> function with the alternate compressors. maintained, filled, packaged, marked, labeled, <br /> 4.9.6 Separators and shipped to comply with current DOT regu- <br /> lations and the American National Standard, <br /> 4.9.6.1 Anentrainmentse <br /> p Method of Marking Portable Compressed Gas <br /> size and design pressure shall be installed in the Containers to Identify the Material Contained, <br /> compressor suction line. The separator shall be Z48.1* <br /> equipped with a drain and gaging device. <br /> ed <br /> 4.9.6.2 An oil separator 5.1.2 Containers ignind table ders shall be <br /> such P in an area free from ignitable debris and in such <br /> be installed in the compressor discharge line. It manner as to prevent external corrosion.Storage <br /> shall be designed for at least 250 psig(1720 kPa) may be indoors or outdoors. <br /> and shall be equipped with a gaging device and <br /> ( drain valve. 5.1.3 Containers and cylinders shall not be <br /> 4.9.7 Condensers buried below ground. <br /> 4.9.7.1 The condenser system maybe cooled 'See Appendix C for availability. <br /> 20 <br />