AMERICAN NATIONAL STANDARD K61.1-1981
<br /> APPENDIX A
<br /> Minimum required rate of discharge in cubic feet per minute of air at 120 per cent of the maximum permitted
<br /> start to discharge pressure for safety relief valves to be used on containers other than those constructed in accord-
<br /> ance with United States Department of Transportation cylinder specifications.
<br /> flow Rata Fiow Rao Fiow Rata Flow Rao
<br /> Surface CFM Surface CFM Surface CFM Surface CFM
<br /> Ars.Sq.FL Air Area.Se.FL Air Arm.Sq.FL Air Arm.Se.FL Air
<br /> 20 258 145 1,310 340 2,640 1,350 8,160
<br /> 25 310 150 1,350 350 2,700 1,400 8,410
<br /> 30 360 165 1,390 360 2.760 1,450 8,650
<br /> 35 408 160 1,420 370 2,830 1,500 8,900
<br /> 40 455 165 1,460 380 2.890 1,550 9,140
<br /> 45 501 170 1,500 390 2,950 1,600 9,380
<br /> 50 547 175 1,530 400 3,010 1,650 9,620
<br /> 56 591 180 1,570 450 3,320 1,700 9,860
<br /> 60 635 186 1,600 500 3,620 1,750 10,090
<br /> 65 678 190 1,640 550 3,910 1,800 10,330
<br /> 70 720 196 1.670 600 4,200 1,850 10,560
<br /> 75 762 200 1,710 650 4,480 1,900 10,800
<br /> 80 804 210 11780 700 4,760 1,960 11,030
<br /> 85 845 - 220 1,860 750 5,040 2,000 11,260
<br /> 90 885 230 1,920 800 5,300 2,050 11,490
<br /> 95 925 240 1,980 850 5,590 2,100 11,720
<br /> 100 965 250 2,050 900 5,850 2,150 11,950
<br /> 105 1,010 260 2,120 950 6,120 2,200 12,180
<br /> 110 1,050 270 2,180 1,000 6,380 2,250 12,400
<br /> 115 1,090 280 2,250 1,050 6,640 2,300 12,630
<br /> 120 1,120 290 2,320 1,100 6,900 2,350 12,850
<br /> 125 1,160 300 2,380 1,150 7,160 2,400 13,080
<br /> 130 1,200 310 2,450 1.200 7,410 2,450 13,300
<br /> 135 1,240 320 2,510 1,250 7,660 2,500 13,520
<br /> 140 1,280 1 330 2,570 1 1,300 7,910
<br /> Surface Area=Total Outside Surface Area of Container in Square Feet.When the Surface Area is
<br /> riot stamped on the name plate or when the marking is not legible,the area can be calculated by using
<br /> one of the following formulas:
<br /> (1) Cylindrical container with hemispherical heads
<br /> Area=overall length in feet times outside diameter in feet times 3.1416.
<br /> (2) Cylindrical container with other than hemispherical heads
<br /> Area=(overall length in feet plus 0.3 outside diameter in feet) times outside diameter in feet
<br /> times 3.1416.
<br /> (3) Spherical container
<br /> Area=outside diameter in feet squared times 3.1416.
<br /> Flow Rate - CFM Air=cubic feet per minute of air required at standard conditions, 60 F and
<br /> atmospheric pressure (14.7 psia).
<br /> The rate of discharge may be interpolated for intermediate values of surface area.For containers
<br /> with total outside surface area greater than 2.500 sq.ft., the required flow rate can be calculated using
<br /> the formula,Flow Rate CFM Air=22.11 A°H1 where A=outside surface area of the container in square
<br /> feet.
<br /> CONVERSION FACTORS:
<br /> ft' x 0. 092 903 = m2
<br /> CFM x 0. 028 317 = ma/min
<br /> ft x 0. 304 8 = m
<br /> 26