Laserfiche WebLink
• April 5,2017 Lab ID : STK1733532 <br /> Live Oak Geo Environmental Customer : 3-16608 <br /> Quality Control - Inorganic <br /> Constituent Method Date/m Type Units Conc. QC Data DQO Note <br /> Wet Chem <br /> urate+Nitrite as N 4500NO3F MS mg/L 11.22 95.0% 5-285 <br /> (CH 1772052-001) MSD mg/L 11.22 96A% 5-285 <br /> MSRPD m /L 11.22 0.9% f30.4 <br /> 450ONO3F 03/30/17:204632JDD CCB mg/L 0.057 0.1 <br /> CCV mg/L 11.22 963% 90-110 <br /> CCB mg/L 0.068 0.1 <br /> CCV m /L 11.22 97.3% 9001110 <br /> Definition <br /> CCV :Continuing Calibration Verification-Analyzed to verify the instrument calibration is within criteria. <br /> CCB :Continuing Calibration Blank-Analyzed to verify the instrument baseline is within criteria. <br /> MS :Matrix Spikes-A random sample is spiked with a known amount of analyte.The recoveries are an indication of how that sample <br /> matrix affects analyte recovery. <br /> MSD :Matrix Spike Duplicate of MS/MSD pair-A random sample duplicate is spiked with a known amount of an dyted.The recoveries <br /> are an indication of how that sample matrix affects analyte recovery. <br /> MSRPD :MS/MSD Relative Percent Difference(RPD)-The MS relative percent difference is an indication of precision for the preparation <br /> and analysis. <br /> D O :Data ua]ity Objective-This is the criteria against which the quality control data is compared. <br /> • <br /> • <br /> Page 7 of 7 <br />