ENGINEERED SEPTIC SYSTEM FOR PAR. 1 & 3 <br /> 28251 E. HWY 26 <br /> LINDEN, CA. 95236 <br /> PA-0600067 <br /> The installation of this system must comply with the standards applicable contained in the EPA <br /> Design Manual, Onsite Wastewater Treatment and Disposal Systems and the Sewage Standards, <br /> Environmental Health Department of San Joaquin County. <br /> MOUND SYSTEM <br /> Base Area=4,000 SF (Min. Requirement). Use 40'x 100',for 3 bedroom residence. Add 1000 <br /> SF for each additional bedroom plus additional laterals. <br /> r <br /> Laterals @ 22'ea, 1/4" holes @ 30", 9 holes/Lateral, (END MANIFOLD) <br /> Lateral vol.. 1.7 gal . <br /> Min. Dose=200 gal. <br /> Manifold-3" Dia. PVC, Sch. 40 <br />+ Dosage 130 gal. <br /> Min. Discharge rate: 13 laterals x 9.4 gpm=15'gpm <br /> TDH: 2.0 Pressure head <br /> 2.09 (100' of 3" PVC) <br /> 8.0 Elev. Head <br /> 16.0 Friction Head(3" angles estimated) <br /> j <br /> Total 28.09'Pumping Head <br /> PUMP: Deliver 75 gpm against 28.09 head. <br /> End manifold used in this design. Could use centralmanifold and reconfigure. <br /> System is to be installed on flat ground (<than 3 % slope) <br /> 3 <br /> Pump and electrical controls by Orenco Systems Inc., 814 Airway Ave.,.Sutherlin, OR.97479„ or <br /> equal. <br />