Laserfiche WebLink
CITY OF TRACY <br /> TRACY Department of Development& Engineering Services <br /> 333 Civic Center Plaza Telephone: (209)831-6400 <br /> Tracy, CA 95376 Fax: (209)831-6439 <br /> Thinl ImiJc Fe Tn'.nGi! <br /> September 22, 2015 <br /> Description: SJCOApplication Number-PA-1500168(SA) <br /> 1. Provide static water supplies (tanks as per NFPA 22) and all drafting <br /> components, piping, valves, signage, etc. as required by the 2013 California Fire <br /> Code (CFC). <br /> 2. Provide fire apparatus access roads to all buildings on site per the 2013 CFC; <br /> meeting requirements related to road capacity of 25,000 pounds per axle, <br /> signage, designated turn around capability, turning radius and show a plan that <br /> shows a fully-implemented parking area for the trucks and business operations. <br /> 3. Provide access through manual gates with a Knox Padlock or Knox Box. If Knox <br /> Padlock are used, Knox Boxes will need to be used at structures. <br /> 4. If gates are automatic, an Opti-Com will need to be implemented along with a <br /> Knox Key Switch, battery back-up or manual means to open gate when power <br /> goes out. <br /> 5. Provide appropriate premises identification at street. <br /> 6. Provide appropriate scheme for each building on site and such addresses shall <br /> also be identified at street. <br /> 7. Provide appropriate fire extinguishers per building. <br /> 8. Provide radio coverage for new building. <br /> Kevin Jorgensen <br /> Chief Building Official <br /> Fire Code Official <br /> City of Tracy <br /> South County Fire Authority <br /> 333 Civic Center Plaza <br /> Tracy, California 95376 <br /> (209)831-6400-office <br /> (209)831-6415-direct <br /> kevin.iorgensen(o)ci.tracv.ca.us <br />