® WorleyParsons <br /> resources&energy <br /> • Transformer temperature (4-20mA) <br /> Each 4.16kV-480V Transformer: <br /> • Common trouble alarm(DI) <br /> Each Medium Voltage Switchgear Lineup: <br /> • Bus voltage (through datalink) <br /> • Main breaker current, kW, and WAR(through datalink) <br /> • Transformer and MCC feeders current, kW, and WAR(through datalink) <br /> • Motor feeders current(through datalink) <br /> • Bus undervoltage indication(DI) <br /> • Instrument voltage transformer blown fuse indication (through datalink) <br /> • I/O as defined on standard schematics <br /> Each 480V Switchgear: <br /> • Ground fault alarm <br /> • Bus phase A-to-B voltage (4-20mA) <br /> • Main breaker phase B current(4-20mA) <br /> 125VDC System: <br /> • One common trouble alarm from each battery charger <br /> • One common trouble alarm from each 125VDC switchboard <br /> • One common alarm from each battery management system <br /> 120VAC UPS System: <br /> • One common trouble alarm from the UPS inverter <br /> • Position of each main breaker/switch on each UPS panelboard <br /> • Manual bypass switch position <br /> 4.18 Controls <br /> 4.18.1 Synchronizing <br /> The CTG and STG will be synchronized automatically from the balance of plant DCS <br /> through the units respective synchronizing system, which is included as part of each <br /> generator package. In addition, the CTG will also be complete with vendor supplied <br /> controls to allow the CTG to be synchronized from the local CTG control room. The <br /> synchronizing system will control turbine speed/generator frequency, generator voltage, <br /> and breaker closure (factoring in breaker historical closure time). No remote manual <br /> synchronizing capability is required. Synchronizing breaker selection will be performed <br /> Lodi Energy Center 3.4- 12 LEC AFC <br /> 071608 Rev.A <br />