Laserfiche WebLink
5.1C:EVALUATION OF BEST AVAILABLE CONTROL TECHNOLOGY <br /> TABLE 5.1C-5 <br /> Recent NOx and CO BACT Determinations for Medium-Sized Auxiliary Boilers <br /> Heat Input <br /> Rating <br /> Facility District/State (MMBtu/hr HHV) NOx Limit CO Limit Date Permit Issued Source <br /> Colusa Generating Station EPA Region 9 44 9 50 May 2008 CEC final decision <br /> Genentech BAAQMD 97 9 50 September 2005 CARB BACT <br /> Clearinghouse <br /> Medimmune, Inc Maryland 29.4 9 n/a January 2008 RBLC# MD-0037 <br /> 0.011 0.036 <br /> CPV Warren Virginia 97 b MMBtu a b MMBtu° January 2008 RBLC#VA-0308 <br /> Minnesota Steel Industries Minnesota 99 Ib/M0.035 <br /> M5 b 0.08 Ib/MMBtud September 2007 RBLC# MN-0070 <br /> Thyssenkrupp Steel and Stainless Alabama 64.9 0.035 b 0.040 August 2007 RBLC#AL-0230 <br /> USA, LLC Ib/MMBtu Ib/MMBtu <br /> Daimler Chrysler Corporation Ohio 20.4 0.0350 b 0.0830 d May 2007 RBLC# OH-0309 <br /> lb/MMB tu Ib/MMBtu <br /> Notes: <br /> a. Equivalent to approximately 9 ppmc NOx. <br /> b. RBLC record shows 0.0035 Ib/MMBtu, but based on rated heat input and hourly limit,this is believed to be a typographical error.This is equivalent to <br /> approximately 27 ppmc NOx. <br /> c. Equivalent to approximately 50 ppmc CO. <br /> d. Equivalent to approximately 100 ppmc CO. <br /> SAC/371322/082330016(LEC_5.1C_APPENDIX.DOC) 5.1C 18 <br />