Laserfiche WebLink
GENERATOR SCHEDULE SYMBOL LIST GENERAL NOTES <br /> GENERATOR MANUFACTURER FUEL NEMA 3R GENERAL: <br /> KW (KVA) VOLTAGE PHASE WIRE LISTING SINGLE LINE DIAGRAM: 1. ALL MATERIALS AND WORKMANSHIP SHALL CONFORM TO THE 2013 CALIFORNIA o r, <br /> STANDBY MODEL CONSUMPTION dB(A)023fT ml <br /> ELECTRICAL CODE, 2011 NATIONAL ELECTRIC CODE AND ALL APPLICABLE LOCAL CODES g <br /> 36.6 GAL/HR 0 YES -I DUPLEX CONVENIENCE OUTLET 15 AMPS, 120VOLTS +15" AND REGULATIONS. '� c6 r, <br /> It <br /> EG1 CATERPILLAR C15 5oo (s25) 277/480V 3 4 FULL LOAD 75.3dB(A) UL 2200 ABOVE FINISH FLOOR UNLESS OTHERWISE NOTED. �N <br /> EMERGENCY DUPLEX CONVENIENCE OUTLET 15 AMPS, 120 150A CIRCUIT BREAKER, MOLDED CASE, 3 POLE, 2. MINIMUM SIZE OF CONDUIT SHALL BE 3/4", MINIMUM SIZE OF CONDUCTOR SHALL BE 9 <br /> OPTIONS REQUIRED: VOLT, +18"A.F.F. 3P 1 150 AMP TRIP. #12 AWG UNLESS OTHERWISE NOTED. <br /> 1. GENERATOR SHALL BE SUPPLIED WITH MCG SURGE PROTECTOR, MODEL 160M-277Y FOR 277/480VAC-3PH, 4W+GND. DOUBLE DUPLEX CONVENIENCE OUTLET +18" ABOVE FINISH I 3. ALL PANELS, SWITCHES, ETC. SHALL HAVE SUFFICIENT GUTTER SPACE AND LUGS TO o $ <br /> 2. GENERATOR MAIN CIRCUIT BREAKER SHALL BE EQUIPPED WITH 12/24V.DC SHUNT TRIP. FLOOR UNLESS OTHERWISE NOTED. 1 SHUNT-TRIP CIRCUIT BREAKER, 3 POLE, 150 ACCOMMODATE CONDUCTORS SHOWN. <br /> 3. PROVIDE WITH NRG INTELLIGENT ENGINE START BATTERY CHARGER 150A AMP TRIP. 4. WHERE WIRE SIZES ARE INDICATED ON PLANS, FOR INDIVIDUAL CIRCUITS, THE WIRE D <br /> 4. PROVIDE BALL VALVE ON BLOCK HEATER EMERGENCY DOUBLE DUPLEX CONVENIENCE OUTLET 3P 1 0 N <br /> 5. PROVIDE COMMON FAIL RELAY +18"A.F.F., U.O.N. SIZE INDICATED SHALL APPLY TO THE COMPLETE CIRCUIT, UNLESS OTHERWISE NOTED. <br /> 6. PROVIDE 12 LEADS RECONNECTABLE GENERATOR owc <br /> 7. PROVIDE DIAL OUT OPTION 0 JUNCTION BOX. N.O. CONTACT OF MICRO SWITCH (LID 5. ALL JUNCTION BOXES AND PULL BOXES SHALL BE OF CODE GAUGE AND OF THE Z CO <br /> 8. PROVIDE LOAD CENTER 70A-MAIN CB, 208/120V-3PH,4W; 20 CIRCUITS IN THE GENERATOR ENCLOSURE, COMPLETE CLOSED). CONTACT SHALL BE CLOSED TO REQUIRED SIZE TO ACCOMMODATE NUMBER OF CONDUCTORS SHOWN. Y a N <br /> PRE-WIRED TO ENGINE BLOCK HEATER, BATTERY CHARGER AND CONTROLS AS REQUIRED. FLUSH MOUNTED LIGHTING AND/OR RECEPTACLE TRIP MAIN BREAKER OF CONNECTED 0 1;; " <br /> 6. ALL PULL BOXES IN FINISHED AREAS SHALL HAVE FACTORY APPLIED PRIME COAT OF N <br /> 9. PROVIDE NEMA 5-20R GFCI SERVICE RECEPTACLE WITH WP COVER AT THE EXTERIOR ENCLOSURE - PRE WIRED TO PANELBOARD. EQUIPMENT UPON OPENING LID. PAINT. • r, fO <br /> LOAD CENTER. O° GROUND WELL WITH 10'-0"L. x 3/4" DIA. COPPER CLAD d m L J <br /> 10. PROVIDE (2) SERVICE LIGHTS (METALLIC VAPOR-PROOF LED TYPE WITH WIREGUARD POLYCARBONATE GLOBE) INSIDE THE GROUND ELECTRODE 70A 1 7. ELECTRICAL CONTRACTOR SHALL VERIFY THE EXACT LOCATION OF ALL EQUIPMENT <br /> ENCLOSURE PRE WIRED THRU WP-TYPE SWITCH TO LOAD CENTER. 800A REQUIRING ELECTRICAL CONNECTION PRIOR TO ANY WORK. <br /> 11. PROVIDE (2) 20A-1P BRANCH CIRCUIT BREAKER READY FOR CONNECTION TO DAYTANK. 103P 3P SWITCH AND FUSE, 3 POLE, 100 AMP WITH . . . . . . <br /> PANEL, SWITCHBOARD TRANSFORMER, OR TERMINAL CABINET (3) 70 AMP FUSES. <br /> 12. PROVIDE (1) 20A-2P AND (2) 20A-1P SPARE BREAKER IN THE LOAD CENTER. 2LA DESIGNATION. 8. ALL PANELBOARDS SHALL HAVE LOCKING DOORS AND BE KEYED ALIKE UNLESS • • • • • • <br /> 13. PROVIDE EMERGENCY OFF PUSH-BUTTON WITH PROTECTIVE COVER PREVENTING UNINTENDED SHUT-OFF. OTHERWISE NOTED. a • • " • <br /> . . . • � • <br /> 2 <br /> . .DEMO REFERENCE NOTE #2. M METERING AND CURRENT/POTENTIAL 9. ELECTRICAL CONTRACTOR SHALL EXTEND WIRING FROM ALL JUNCTION BOXES, . • o• <br /> TRANSFORMER AS REQUIRED. RECEPTACLES, SWITCHES, ETC. AND MAKE FINAL CONNECTION AS REQUIRED TO ALL <br /> NEW REFERENCE NOTE #2. BUILDING EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS. 'm <br /> DIESEL FUEL TANK SCHEDULE CONDUIT CONCEALED IN CEILING OR IN WALLS. 10, ALL MOUNTING HEIGHTS SHOWN ARE TO CENTER LINE OF OUTLET OR DEVICE AND <br /> GROUND FAULT SENSOR. SHALL APPLY UNLESS INDICATED OTHERWISE. <br /> TYPE CAPACITY DOUBLE WALL LEAK DETECTION FIRE RATED LISTING --------------------- CONDUIT EXPOSED 11. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND <br /> WORK INCLUDED. FOLLOW DRAWINGS IN LAYING OUT WORK AND CHECK DRAWINGS OR <br /> DAY-TANK 200 GALLON YES YES 2 HOUR UL142 ------- CONDUIT BELOW FLOOR OR UNDERGROUND USE RIGID STEEL OTHER TRADES RELATING TO WORK TO VERIFY SPACE IN WHICH WORK WILL BE _ <br /> CONDUIT FOR STUB-UPS, 90-DEGREE BENDS AND RISERS TRANSFORMER WITH SECONDARY GROUND. o INSTALLED. MAINTAIN HEADROOM AND SPACE CONDITIONS AT ALL TIMES. W <br /> OPTIONS REQUIRED: <br /> TO GRADE FROM PVC SCHEDULE 40 UNDERGROUND ,, <br /> RACEWAY. 12. LOCATION OF LOCAL WALL SWITCHES ARE SUBJECT TO MODIFICATIONS. AT OR NEAR <br /> 1. DAY TANK EQUIPPED WITH DUPLEX LEAD-LAG ALTERNATING FILL PUMPS/ MOTORS, EACH RATED 1/3HP-120VAC. AND DUPLEX RETURN 12. <br /> INSTALL SWITCHES ON SIDE OPPOSITE TO DOOR HINGE. VERIFY FINAL HINGE <br /> PUMPS/ MOTORS, EACH RATED 1/3HP-120VAC. - 0 CONDUIT TURNING UP, LOCATION IN FIELD PRIOR TO ANY WORK. <br /> 2. ALTERNATING CONTOLLERS SHALL BE SUPPLIED WITH THE DAY-TANK MANUFACTURED, PREWIRED TO MOTORS AS REQUIRED WITH F R_F; FEEDER NO. 6 - SEE FEEDER SCHEDULE. <br /> STARTERS AND OVERLOAD PROTECTIONS. CONDUIT TURNING DOWN. 13. EXPOSED RACEWAYS (WHEN INDICATED ON DRAWINGS) SHALL BE RUN PARALLEL WITH <br /> 3. CONTROLLER HAS A DUAL INPUT TERMINAL CONNECTION OF 120V-1PH POWER AT 20A DEDICATED CIRCUIT EACH. OR AT RIGHT ANGLES TO WALLS. <br /> 4. REFER TO PLUMBING DRAWINGS FOR ADDITIONAL REQUIRED OPTIONS. GROUND WELL WITH ROD. <br /> L CONDUIT SYSTEM WITH INSULATED GROUND CONDUCTOR. 14. FURNISH APPROVED EXPANSION AND DEFLECTION FITTINGS WHERE RACEWAY CROSSES <br /> Ii GROUND TO COLD WATER PIPE, U.O.N. BUILDING EXPANSION JOINTS. r2 N <br /> 3/4"C.- 2 #12. 3/4"C.- 5 #12. UFER GROUND. 15. FURNISH FISH WIRE IN EACH RACEWAY RUN OVER 10'IN LENGTH, IN WHICH Z n a �+ <br /> „ PERMANENT WIRING IS NOT INSTALLED. 1-•i <br /> -�- 3/4 C.- 3 #12. ��- 1"C.- 6 #12. N NEUTRAL BUS. OD <br /> MANUAL TRANSFER SWITCHBOARD BETWEEN STAND-BY AND PORTABLE GENSET H- 3/4"C.- 4 #12. 1"C.- 7 #12. 16. NOT MORE THAN THREE LIGHTING OR CONVENIENCE OUTLET CIRCUITS ARE PERMITTED F .•-I <br /> MANUFACTURER WIRE ISOLATION G EQUIPMENT GROUND BUS. IN ONE CONDUIT, I INLESS OTHERWISE INDICATED. 0.j 0 <br /> MODEL AMPS VOLTAGE PHASE ENCLOSURE DELAYED LISTING = 17. PROVIDE PULL BOXES WHEREVER NECESSARY TO FACILITATE PULLING OF CONDUCTORS. O <br /> (POLE) BYPASS CONDUCTORS OTHER THAN 12 AWG AS INDICATED 3 6 AWG <br /> # ( # ) COORDINATE LOCATIONS OF BOXES WITH OTHER TRADES TO AVOID CONFLICT. <br /> W.A. BENJAMIN 800 277/480V 3 4+G NEMA 3R NO NO UL 1008 #6 CONDUIT SIZE AS PER N.E.C. 1--1 c <br /> "MTS" - RAINTIGHT MECHANICAL 18. SUPPORT PANELBOARDS, JUNCTION AND PULL BOXES INDEPENDENTLY TO BUILDING " a <br /> MANUAL TRANSFER LUG STRUCTURE WITH NO WEIGHT BEARING ON RACEWAYS. �1 <br /> SWBD CONNECTIONS 2LA-1&3&5 HOMERUN TO PANEL "2LA". CIRCUITS 1,3,5. (3-POLE CIRCUIT `y b 4 <br /> BREAKER) 19. ALL EXTERIOR ELECTRICAL DEVICES AND EQUIPMENT SHALL BE WEATHERPROOF, NEMA U <br /> 3R TYPE. 17) <br /> STANDARD FEATURES: ALL OUTDOOR RACEWAY, CONTROL PANEL, AND EQUIPMENT CONNECTIONS SHALL BE <br /> 2LA-2,4,6 HOMERUN TO PANEL "2LA", CIRCUITS 2,4,6 WITH COMMON NEUTRAL. USING SEALED TYPE FITTINGS, CONNECTORS, MEYER HUBS, LIQUIDTITE (AS <br /> 1. 800A-3P, NON AUTO CB WITH MIN. 50,000 AIC SYM 0480VAC - FOR THE STANDBY MANUAL TRANSFER BREAKER. FOR OUTDOOR INSTALLATION. <br /> 2. 80OA-3P, AUTO CB WITH ADJUSTABLE LSIG ELECTRONIC TRIP UNIT, MIN. 50,000 AIC SYM 0480VAC - FOR APPLICABLE FOR VIBRATION ISOLATION) 0 <br /> PORTABLE MANUAL TRANSFER BREAKER. CONDUIT STUB WITH CAP WITH POLY-PROPYLENE PULL WIRE). 20. WHERE MOUNTING HEIGHTS OR DIMENSIONS OF DEVICE LOCATIONS ARE SHOWN, IN-1 <br /> 3. PILOT <br /> NICALLIGHT KIRK-KEY INTERLOCK BETWEEN TRANSFER BREAKERS. ( ) CONTRACTOR SHALL CONFIRM SUCH DIMENSIONS WITH ARCHITECTURAL DRAWINGS. N <br /> 4. PILOT LIGHTS INDICATOR WITH PROTECTION FUSE, FOR GENERATOR OPERATING STATUS. WHERE CONFLICT IN DIMENSIONS OCCUR BETWEEN DRAWINGS, OR WHERE NO M+1 <br /> 5. PHASE SEQUENCE METER FOR PORTABLE GENSET LINES SIDE WITH FUSE PROTECTION. DIMENSIONS OR MOUNTING HEIGHTS ARE INDICATED ON EITHER SET OF DRAWINGS, W <br /> 6. BUS BARRIER BETWEEN PORTABLE GENSET PHASES <br /> BUS LUGS AND THE LOAD & STANDBY GENSET BUS. 2LA-1-3-5 HOMERUM TO PANEL "2LA". CIRCUIT 1, 3, 5 WITH SEPARATE CONTRACTOR SHALL VERIFY THESE ITEMS WITH ARCHITECT IN FIELD PRIOR TO <br /> 7. SILVER PLATED CU-BUSS FOR ALL PHASES AND NEUTRAL II�FI� NEUTRAL FOR EACH CIRCUIT. ROUGH-IN. <br /> 8. CU GROUND BUS WITH SERVICE BONDING JUMPER (TO NEUTRAL BUS) PROVISION. <br /> 9. MICRO-SWITCH WITH 1.N.0. CONTACT AT THE PORTABLE GEN-SET CABLE ACCESS WINDOW LID. 21. ALL CONDUIT PENETRATIONS THROUGH FIRE RATED WALLS AND FLOORS SHALL BE <br /> 10. RAINTIGHT, NEMA 3R ENCLOSURE, ASA61 UL LISTED POWDER COATING FINISH CABINET. PROTECTED BY MATERIALS TESTED IN ACCORDANCE WITH UL1479/ASTM E- 814. <br /> OPTIONS REQUIRED: INSTALLATION SHALL FOLLOW MANUFACTURER'S INSTRUCTIONS AND MAINTAIN THE FIRE <br /> RATING OF WALLS AND/OR FLOORS AFFECTED. PROVIDE HILTI C5240 FIRESTOP 4 <br /> 1. PORTABLE GENSET AUXILIARY PORTABLE CABINET MOUNTED ON THE SIDE OF SWITCHBOARD WITH THE FOLLOWING FEATURES; MISCELLANEOUS: SEALANT, CSFM LISTING NO. 4060-1200:100, OR EQUIVALENT STATE FIRE MARSHAL <br /> A. 10 POSITION CONTROL TERMINAL BLOCKS APPROVED AND LISTED MATERIAL. <br /> B. 2 POSITION CONTROL TERMINAL BLOCKS (E) WHEN SHOWN ADJACENT TO LIGHTING FIXTURE, OUTLETS, <br /> C. 2 NEMA L5-30R, 30A-120V RECEPTACLE, HUBBELL CAT. 2610A PANELS, IN CONDUIT RUNS, ETC., DENOTES EXISTING TO 22. ANCHORAGE OF ALL EQUIPMENT TO BE INSTALLED, AS A PART OF THIS PROJECT <br /> D. 1 NEMA L6-20R, 20A-208V RECEPTACLE, HUBBELL CAT. 2320A (ER) REMAIN. SHALL BE DETAILED ON THE STRUCTURAL PLANS, EXCEPT FOR THIS FOLLOWING: A <br /> E. 1 NEMA 5-20R, 20A-120V RECEPTACLE, HUBBELL CAT. 5361 A. EQUIPMENT WEIGHING LESS THAN 400 POUNDS SUPPORTED DIRECTLY ON THE <br /> WHEN SHOWN ADJACENT TO LIGHTING FIXTURE, OUTLETS, FLOOR OR ROOF. <br /> PANELS IN CONDUIT RUNS, ETC., DENOTES EXISTING TO BE FURNITURE (NON FIXED AND MOVABLE AS EXEMPTED BY THE CBC 2007 APPENDIX <br /> ABBREVIATIONS <br /> (RE) DISCONNECTED AND RELOCATED. B. CHAPTER 1 SECTION 105.2) 6 <br /> (R) WHEN SHOWN ADJACENT TO ELECTRICAL EQUIPMENT DENOTES C. TEMPORARY OR MOVABLE EQUIPMENT (NON FIXED AND MOVABLE AS EXEMPTED BY <br /> NEW LOCATION OF RELOCATED EQUIPMENT. THE CBC 2007 APPENDIX CHAPTER 1 SECTION 105.2) <br /> DEMOLITION & ALTERATION NOTES A AMPERE NF NON-FUSED D. EQUIPMENT WEIGHING LESS THAN 20 POUNDS SUPPORTED BY VIBRATION <br /> WHEN SHOWN ADJACENT TO ELECTRICAL EQUIPMENT DENOTES AFF ABOVE FINISHED DOOR NIC NOT IN CONTRACT ISOLATORS. <br /> DISCONNECT AND REMOVE EQUIPMENT WITH ASSOCIATED NL NIGHT LIGHT E. EQUIPMENT WEIGHING LESS THAN 20 POUNDS SUSPENDED FROM A ROOF OR <br /> CONDUIT AND WIRING U.O.N. C CONDUIT NTS NOT TO SCALE FLOOR OR HUNG FROM A WALL. <br /> CO CIRCUIT BREAKER PERMANENT EQUIPMENT IN ITEMS A, D, AND E MUST BE SUPPORTED AND ANCHORED <br /> 1. CONTRACTOR SHALL VISIT THE SITE AND MAKE HIMSELF THOROUGHLY FAMILIAR WITH THE EXISTING CONDITIONS. C CIRCUIT PNL PANEL <br /> CO CONDUIT ONLY pWR POWER TO RESIST THE FORCES PRESCRIBED BY CHAPTER 13 OF ASCE 7 AS MODIFIED BY <br /> 2. ALL WORK SHALL BE PERFORMED TO CHANGE THE EXISTING ELECTRICAL INSTALLATION AS INDICATED OR AS REQUIRED TO THE CBC 2007 SECTIONS 1613A/1614A AND THE ANCHORAGE SHALL BE APPROVED <br /> PERFORM THE NEW WORK. DWG DRAWINGS REQ'D REQUIRED BY THE APPROPRIATE DESIGN PROFESSIONAL OF RECORD AND OSHPD AS A PART OF <br /> FIELD REVIEWS/OBSERVATIONS. THE INSPECTOR OF RECORD SHALL ASSURE THAT THE <br /> 3. REMOVE ALL LIGHT FIXTURES, SWITCHES, SPEAKERS, TELEPHONE OUTLETS, RECEPTACLES, MISCELLANEOUS CONDUIT, WIRE, ETC. ELEC ELECTRICAL SHT SHEET ABOVE REQUIREMENTS ARE ENFORCED.EQUIP EQUIPMENT SURF SURFACE z <br /> THAT INTERFERES WITH NEW CONSTRUCTION. EXTEND ANY INTERRUPTED CIRCUITS. PROVIDE BLANK COVER PLATES AS REQUIRED EMERG EMERGENCY sw SWITCH 23. CONTRACTOR SHALL PROVIDE SERVICES FOR AN INTERNATIONAL SEISMIC APPLICATION o <br /> a <br /> IN FINISHED AREAS, COVER PLATES SHALL MATCH THE WALL SURFACE. EXIST EXISTING <br /> TECHNOLOGY (ISAT) REPRESENTATIVE TO PREPARE SHOP DRAWINGS FOR OSHPD <br /> 4. INFORMATION GIVEN ON THE DRAWINGS ABOUT EXISTING INSTALLATIONS HAS BEEN OBTAINED FROM THE BEST SOURCES AVAILABLE F FUSE TC TIME CLOCK REVIEW AND APPROVAL OF THE FOLLOWING: <br /> BUT CANNOT BE GUARANTEED ACCURATE IN ALL RESPECTS. VERIFY ALL SUCH INFORMATION BEFORE PROCEEDING WITH ANY NEW FA FIRE ALARM TYP TYPICAL A. SEISMIC RESTRAINTS SYSTEM FOR ELECTRICAL RACEWAY AND BACK BOXES NOTED <br /> WORK THAT MAY BE AFFECTED. INCLUDE AS A PART OF THE CONTRACT ALL WORK REQUIRED TO PRODUCE THE INDICATED ON THE ELECTRICAL DRAWINGS IN ACCORDANCE WITH APPLICABLE CODES. <br /> FLOUR FLUORESCENT a v m <br /> RESULT. XFMR TRANSFORMER = Q <br /> GA GROUND FAULT INTERRUPTER 24. THE INTENT OF THE DRAWINGS AND SPECIFICATIONS SHALL BE TO RECONSTRUCT THE �s <br /> 5. EXCEPT AS MAY BE SPECIFICALLY INDICATED OTHERWISE, ALL ELECTRICAL MATERIALS AND EQUIPMENT REMOVED FROM THE GRD GROUND UON UNLESS OTHERWISE NOTED AREA OF WORK TO COMPLY WITH APPLICABLE CALIFORNIA BUILDING STANDARD CODE, <br /> EXISTING INSTALLATION IN THE COURSE OF PERFORMING THE INDICATED WORK AND NOT INDICATED TO BE REUSED SHALL BE TITLE 24, CALIFORNIA CODE OF REGULATIONS. SHOULD ANY CONDITION DEVELOP NOT w <br /> TREATED AS FOLLOWS: IC INTERCOM V VOLT COVERED BY THE APPROVED PLANS OR SPECIFICATIONS IN THE AREA OF WORK NOT p <br /> A. ALL CONDUITS, CONDUCTORS, OUTLET BOXES AND FITTINGS SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL IN COMPLIANCE WITH APPLICABLE TITLE 24, CALIFORNIA CODE OF REGULATIONS. z <br /> BE REMOVED FROM THE SITE. LCL LONG CONTINUOS LOAD W/ WITH -� <br /> B. ALL OTHER REMOVED ITEMS SHALL BE TURNED OVER TO THE OWNER AND DISPOSED OF AS DIRECTED BY THE OWNER. LTG LIGHTING WP WEATHERPROOF yy- �� � �m Z H <br /> MIN MINIMUM 4/S JUNCTION BOX 4" SQUARE 6 It W a <br /> 6. CLEAN ALL REMOVED ITEMS THAT ARE TO BE REUSED, CONDUITS THAT ARE TO BE REUSED SHALL BE CLEANED BEFORE MTG MOUNTING 5/S JUNCTION BOX 4-11/16" cj .4 cc <br /> INSTALLING ANY NEW CONDUCTORS. WHERE A CHOICE IS POSSIBLE, SELECT THE BEST OF THE REMOVED ITEMS FOR REUSE. AUG 31 2015 0 p M <br /> 7. UNLESS NOTED OTHERWISE ON THE DRAWINGS, ALL EXISTING WIRING, CONDUITS, JUNCTION BOXES AND OTHER ELECTRICAL ENVIRONMENTAL ,? cko <br /> DEVICES IN AREAS WHERE NEW WORK OCCURS, SHALL BE REMOVED EXCEPT WHEN SUCH DEVICES ARE REQUIRED TO MAINTAIN <br /> SERVICES TO OTHER AREAS. IN SUCH CASES, CONTRACTOR SHALL RELOCATE THESE DEVICES WHERE REQUIRED TO ACCOMMODATE SHEET INDEX r_e Tu nc�noT�rcn - J z U <br /> NEW WORK. CONTRACTOR MAY ABANDON IN PLACE ANY OF THE EXISTING ITEMS WHEN SUCH ITEMS ARE CONCEALED AND DO NOT Q" U <br /> INTERFERE WITH THE NEW WORK OF ALL TRADES. v U v <br /> 8. NUMBER OF CONDUCTORS SHOWN ON EXISTING CONDUITS REPRESENT THOSE REQUIRED TO PERFORM THE WORK. WHEN NUMBER Sheet ISSUE FOR BID 11 /19/14 W M <br /> OF EXISTING IS INADEQUATE, CONTRACTOR SHALL PROVIDE ADDITIONAL WIRES AND ALL NECESSARY WORK AND ACCESSORIES w z c <br /> REQUIRED TO CONFORM TO THE NUMBER OF CONDUCTORS SHOWN ON THE DRAWINGS. ALL EXTRA EXISTING WIRES SHALL BE Sheet Title <br /> TAPED, COILED AND TAGGED AS "NOT-USED" AT BOTH ENDS IN JUNCTION BOXES. CONTRACTOR SHALL EXAMINE AND REPLACE Number <br /> ALL EXISTING WIRES IN BAD CONDITION WITH EQUIVALENT NEW ONES. E-1 ELECTRICAL LEGENDS, GENERAL NOTES &ABBREVIATIONy <br /> pROFESSIp <br /> 9. CONTRACTOR SHALL EXERCISE EXTREME CAUTION OF NOT DAMAGING EXISTING ELECTRICAL SYSTEMS. REFER TO SPECIFICATION E-2 SINGLE LINE DIAGRAM & SCHEDULES g�ooREw H. Y dH A 3 CALl', FJ J013 � 40219.00 <br /> SECTION NOTE #16 ON DRAWING #E-8.1 FOR ADDITIONAL REQUIREMENTS. �Q' No rc ppm <br /> E-3 ELECTRICAL DEMOLITION PLAN E-13884 M 11-02-14 <br /> 6/ M a <br /> E-4 ELECTRICAL PLAN - NEW WORK p. 3 MOS. ARROYO PARKWAY <br /> NO. 100 <br /> y crR\ PASADENA, C.& 91106 E - 1 <br /> OF CAST TEL- (626) 446-8680 <br /> PAS: (626) 445-8081 8 <br />