Laserfiche WebLink
LDT 5000 Field Test Apparatus Page 1 of 1 <br /> 440 Tanknology Line Leak Detector Test <br /> Work Order: 2341089 Date : 7/9/2019 <br /> Site Name / ID : 7- ELEVEN # 17647 , MKT 2368 ( W744) / 17647 <br /> Address : 1048 W. YOSEMITE AVE @ EL PORTEL <br /> City : MANTECA State : CA Zip : 95336 <br /> Tank ID T-1 T-2 <br /> Product RUL PUL <br /> Product Line 1 1 <br /> Tested From 3 3 <br /> Existing/New Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical <br /> Manufacturer/Model Veeder Root FX1 V Veeder Root FXi V <br /> Serial No . 11002 6195 116056 40710 4609 11605 <br /> Pump Operating Pressure (psi ) 28 . 00 28 . 00 <br /> Calibrated Leak (ml/min ) 189 . 0 189 . 0 <br /> Calibrated Leak (gph ) 3 . 00 3 . 00 <br /> Holding PSI 28 . 00 18 . 00 <br /> ' N/A for Electronic LD's <br /> Resiliency (ml ) 150 . 00 130 . 00 <br /> ' NIA for Electronic Lo's <br /> Metering PSI 10 10 <br /> ` NIA for Electronic LD' s <br /> Opening Time (sec) 2 2 <br /> ' N/A for Electronic LD's <br /> Fest Results Pass Pass <br /> Technician Comments : <br /> Technician Name : Jarrod Cooke Certification #: 2081 <br /> Technician Signature : Expire Date : 4/11 /2021 <br /> Environmental Compliance for Petroleum Systems <br /> © 2019 Tanknology Inc, Austin, TX. All rights reserved. tanknology.com <br />