Jul 1719,06:42p Pro Lube Inc 209 3851235 p.8 <br /> Hazardous Waste Tank System <br /> Written Assessment per CCR Tide 22 September' <br /> Pro Lube. 808 S. Cherokee Lane Lodi, CA 95240 2018 <br /> Tank Assessment Page Tank Name/marking: Used Oil Tank <br /> Tank age: 26 years estimated <br /> Manufacturer. Unknown <br /> Remaining service Iife: 25 years, inspect <br /> in 5 years <br /> Tank Construction: <br /> Shape: Rectangular, Flat bottom, closed top. <br /> Orientation: Vertical, double wall. <br /> Location (abovelbelow ground): Above ground <br /> Design Standard: UL142 <br /> Material of construction: steel <br /> Thickness and method to determine: 0.15" by UTG. <br /> Lining material &thickness (if applicable): N. A. <br /> Corrosion Protection equipment: Compatible <br /> Structural support: The tank rests on concrete foundation. <br /> Other identifying features: White <br /> Piping and ancillary equipment(pumps): Qty, 1 <br /> Piping Material of Construction: copper/ rated hose <br /> Piping Diameter: V <br /> Pump location(s): Within 5" of tank in garage. <br /> Pump types)/capacities: ACID, 10 gpm <br /> Overfill Protection: B&J 007 with alarm. <br /> Material Storage: <br /> Material and characteristics: Used Motor Oil, non-RCRA, Class III B <br /> Combustible <br /> Specific Gravity: 0.95 <br /> Operating Capacity: 928 gallons <br /> Strandberg Associates 1(8661 336-u404S r'.5rat81U41'•i�1y�;_._..,_�.:—C,:' <br /> 7 <br />