i <br /> IProject 01250.02 27 March 1991 <br /> Phase Source Test Source Test Source Test <br /> I System Incinerator Incinerator Incinerator <br /> Test Date 3/8/91 <br /> TOTAL SYSTEM <br /> Outlet Temp OF 690 <br /> IChange in Temp °F 60 <br /> Vacuum ("Hg) 1 .75 <br /> F1owrate (scfm) 91.4 , <br /> Influent TVH (ppm) 1 ,800 <br /> Influent TVH --- --- <br /> Rate (lb/day) 59 2 <br /> Effluent TVH (ppm) 200 --- --- <br /> Effluent TVH <br /> Rate (lb/day) 6.6 <br /> Detection Limit --- --- --- <br /> (ppm) 1.0 <br /> Method GC FID <br /> BENZENE <br /> Flowrate (scfm) 914 - - -- <br /> Influent Benzene - <br /> Conc (ppm) 25 <br /> Influent Benzene --- --- --- <br /> Rate (lb/day) 0 8 <br /> Effluent Benzene --- --- --- <br /> Conc. (ppm) 3 5 <br /> Effluent Benzene --- --- --- <br /> Rate (lb/day) 0 09 <br /> Detection Limit 2 5 <br /> - --- --' <br /> (ppm) 0 2 <br /> *Method GC FID <br /> Vacuum - System vacuum in inches of Mercury. <br /> scfm - Standard cubic feet per minute. <br /> * - Modified EPA Method 8020. <br /> NT - Not tested <br /> ND - Not detected <br /> I <br /> 3 - <br /> I <br />