Laserfiche WebLink
MS-98-43 <br /> Page 2 <br /> D. Construction of individual domestic water well under permit and inspection by the <br /> Environmental Health Division is required at the time of development. (San Joaquin <br /> County Development Title Section 9-1115.3). <br /> E. The existing private water wells shall be tested for the chemical dibromochloropropane <br /> (DBCP) and nitrates prior to recordation of the Parcel Map. Samples are to be taken and <br /> analyzed by a State-approved laboratory. (San Joaquin County Development Title <br /> Section 9-111�.7). <br /> F. The well must be repaired under permit and inspection by the Environmental Health <br /> Division(San Joaquin County Development Title Section 9-1115.4(e)) as follows: <br /> Agricultural discharge pipes utilizing an air gap for backflow prevention shall maintain <br /> an air gap equal to the size of the discharge pipe, but not less than 6 inches. The <br /> discharge pipe shall also have two `/4 inch slits extending 6 inches from the bottom of the <br /> pipe and opposite each other or a backflow device approved by San Joaquin County must <br /> be installed. <br />