Laserfiche WebLink
.• .• .r =E.�;.., ;ci:=1P,t',`�:SR��,�:4;;;��''' ... fit' <br /> ' •b.'•'r;.r,.v"�"�:•^ ,'�iu 4u Q� �'`4c.� '.fru r1 r ,fk �. <br /> • .. ,. .... ,.. ...... ... ......Lk..'.... v.!.._..,4 df.:'.,r:3 ,i'.i:ae.L."ru ...1.�.:.y..r.�rN:t+'ir.:r M �. ` +'V <br /> I The OPW 61SO Overfill Prevention Valve is designed to prevent the overfill of underground <br /> storage tanks by providing a positive shut-off of product delivery.The shutoff valve is an integral <br /> part of the drop tube used for gravity filling.The OPW 61SO allows easy installation(without <br /> 11 breaking concrete)and requires no special manholes. <br /> The OPW 61 SO is a two-stage shut-off valve. When the liquid level rises to about 950/,of tank <br /> capacity, the valve mechanism is released, closing automatically with the flow.This reduces the <br /> flow rate to approximately 5 gpm through a bypass valve.The operator may then stop the filling <br /> process and disconnect and drain the delivery hose.As long as the liquid exceeds the 95%level, <br /> the valve will close automatically each time delivery is attempted. <br /> If the delivery is not stopped and the liquid rises to about 98%of tank capacity, the bypass <br /> valve closes completely. No additional liquid can flow into the tank until the level drops below a tta LIIPIJ8,D <br /> reset point. w .a <br /> Models of the 61 SO are available to meet virtually any UST application including two-point, �– <br /> coaxial,poppeted coaxial and remote fill.The 61SO-3000 provides two-point overfill protection for f� ' ` <br /> 3"riser pipes,and the 61SO-1000 and 61SO-100C(CARS)feature a grooved-tube design for use <br /> with tank gauging systems.Methanol and CARS(vapor-tight)approved models are also available, Look krftr%WAV&d,&Vdk <br /> The OPW 61$0 is approved by the New York City Fire Department,(Approval#4902). OPW W*'°m#dMid= <br /> Features: <br /> ♦ Simple,Easy and Quick Installation- ♦ No Pressurization of the Tank- <br /> No excavation or special manholes Operates directly from liquid level. <br /> required. *Will Accept a Dipstick for Gauging. <br /> * Economical-Costs a fraction of ♦ Retrofits Directly-For both new and <br /> expensive, complicated and difficult- existing tanks with 3"or 4"fill risers. Certification NY City Fire <br /> tc,4nstall valves, ♦ Quick Drain Feature-Automatically and Listings CARE Department EVR <br /> i Furnished Complete-Supplied with new drains hose when head pressure is <br /> upper and lower drop tubes, relieved. 6950 Series Initial Approval <br /> mounting hardware and thorough ♦ gest Flow hate in The Industry.' Certification 44902 VR-102 <br /> instructions for quick job site time. Letter Oct 88 <br /> (' * Completely Automatic Operation-No. Updated Approval <br /> prechecks to perform,no resets,and no "Test-witnessed by Bowser-Momer,Inc.,an latter#97-04 <br /> overrides to be broken or abused. independent laboratory.Results available <br /> upon request. 61SOM Approval <br /> Letter NM VR-102 <br /> 61$0P Approval -- — <br /> Materials Seals:Witton' Letter#92-8 <br /> Valve body:cast aluminum Upper&lower Drop Tube: aluminum <br /> Float: nitrile rubber, closed cell foam Plastic parts: acetal <br /> Valve:aluminum Hardware:stainless steel <br /> IMPORTANT <br /> in order to prevent product spillage <br /> from the Underground Storage Tank <br /> (UST),properly maintained delivery <br /> Advantages of Overfill Prevention equipment and a proper connection at <br /> the tight-fill adaptor are essential. <br /> Compared .to Overfill Warning Systems: Delivery personnel should be managed <br /> and trained to inspect delivery elbows <br /> ♦Completely Automatic Operation- ♦Speeds Delivery Operations- and hoses for damaged and missing <br /> Does not rely on the alertness or speed Product flows unimpeded into the tank 'parts.They should always make certain <br /> of response of the delivery attendant until the hose"kick"that accompanies there is a positive connection between <br /> for certainty of overfill prevention. the valve shut-off provides a clear the adaptor and elbow. If delivery <br /> ♦ Keeps the Top of UST"Dry,"per signal that the liquid has reached the equipment is not properly maintained, <br /> EPA Requirements-Eliminating shut-off level, or the elbow is not securely coupled to <br /> possible leaks at loose bung fittings ♦Simple and Inexpensive Installation- the adaptor,a serious spill may result <br /> when the OPW 6150 closes, <br /> and the need for double containment In both two-point and coaxial fill causing a hazard and <br /> on vent lines. applications, no additional excavation, envirownental contamination. <br /> i ♦ Does Not Rely on Pressure in the manholes or vent piping are required. NOTE: The OPW 61SO is designed for <br /> UST to Stop Flow-Allowing faster fill use on tight-fill gravity drop <br /> times and reducing spill risk, applications only. Do not use <br /> for pressure till applications. <br /> North AmodLa Too Fred-TLELEP14ONE:tS90 422.2626 F :(800)421.3297 EmeiL'daireaflEealeap)opw•fc.czri <br /> �.� gtiAmMlo nal-T2Ll;PHONE:(673}61'tIJ31$or(513 tl7IF3261�Fxz:1519`870.9157 a Enual:inYsxldd�iapvo-fc.corn <br /> WM40SOU fcc>tr, Diu <br /> r ti uuutnj�-w...0 U CopyI19M 2�J65,OPW FudAng Camporar.�*P•O.Buz dD5QU3*gfiCh q,atl,OH G52d0.5003-Flllletl ht USA W 9105 �.Jk.Y� <br /> 60 39Vd '00 B 63di9dH `G73IHS b688ZL69TST VT :9T 50aZ/60/Z0 <br />