Laserfiche WebLink
Test Date: 11/27/2002 <br /> SECONDARY CONTAINMENT TEST RESULTS Work Order: 2224684 <br /> SUMP TESTS <br /> Tank or Disp Model or Diam./Width/Length Depth Start Initial Level Finish Final Pass/ <br /> Type Manufacturer Test Method <br /> # Material (") (") Time Level Chane Time Result Fail <br /> Dispenser Sump 1/2 Containment Fiberglass 20" 32" Hydrostatic-VPLT 1253 10" 0.00190 1309 0.001 gph Pass <br /> Dispenser Sump 3/4 Containment Fiberglass 20" 32" Hydrostatic-VPLT 1250 10" 0.00001 1306 0.001 gph Pass <br /> Dispenser Sump 5/6 Containment Fiberglass 20" 32" Hydrostatic-VPLT 1310 10" 0.00045 1326 0.010 gph Pass <br /> Dispenser Sump 7/8 Containment Fiberglass 20" 32" Hydrostatic-VPLT 1333 10" 0.00004 1349 0.001 gph Pass <br /> Comments: <br />