Laserfiche WebLink
PP TankrxWoqy <br /> SECONDARY CONTAINMENT TEST RESULTS <br /> SITE NAME: UNITED GAS 440 W Charter DATE:1 10/14/2002 WORK ORDER 2224136 <br /> SITE ADDRESS: 440 W CHARTER WAY STOCKTON CA 95206 <br /> REASON FOR TEST: SB-989 3-YR Groundwater Level("from grade): <br /> TANK INFORMATION AND INTERSTITIAL TESTS <br /> Dia. Depth Start Initial Finish Final Pass/ <br /> Tan Product Tank Size Material Manufacturer ( ) Test Method Time Level Time Result Fail <br /> 1 REGULAR 20000 128 FRP CLD ST Trusco n/a Vacuum 1030 7 "Hg 1130 4 "Hg FAIL <br /> 2 SUPREME 10000 96 FRP CLD ST Trusco n/a Vacuum 1030 7 "H9 1130 3.5 „Hg FAIL <br /> 3 0 0 <br /> 4 <br /> 5 <br /> 6 <br /> 7 <br /> 8 <br /> Comments: <br /> LINE INFORMATION AND INTERSTITIAL TESTS <br /> Dia. Len. Volume Start Initial Finish Final Pass/ <br /> Tan Product Material Manufacturer Test Method <br /> feet allons Time Level Time Result Fail <br /> 1 <br /> 2 <br /> 3 <br /> 4 <br /> 5 <br /> 6 <br /> 7 <br /> 8 <br /> Comments: No tested <br />