Laserfiche WebLink
• AFFOP.DA-TE$T 209 794 0112 P. 02 <br /> INVOICE #J5000462 TEST DATE: 02/24/*� <br /> AFF'ORBA^TEST <br /> POB 36 - 26515 N SACRAMENTO 13L <br /> THORNTON, CA 95686-0036 <br /> (209)794-0102 FAX (209)794-0112 <br /> TANK STATUS EVALUATION REPORT <br /> ----------------------------- <br /> ***** CUSTOMER DATA ***** ***** SITE DATA ***** <br /> FILLNER CONSTRUCTION, INC. UNITED GAS <br /> 3633 SEAPORT BLVD. 440 W. CHARTER WAY <br /> @ LINCOLN ST. <br /> WEST SACRAMENTO, CA. STOCKTON, CA. <br /> 95691 95206 <br /> CONTACT: KIETH CONTACT: MR. GILL <br /> PHONE #: (916)372-l9B5 PHONE #: (209)465-2487 <br /> ***** COMMENT LINES ***** <br /> 20K RUL & 10K SUP - PRESSURE SYSTEM - BALANCED VR <br /> GILBARCO EMC ATG - TESTTIMES ARE 135 & 90 MINS. RASPECTIVELY <br /> CURRENT EPA STANDARDS DICTATE THAT FOR UNDERGROUND FUEL TANKS, THE <br /> THE MAXIMUM ALLOWABLE HOURLY LEAK/GAIN RATE IS .05 GALLONS. <br /> ULLAGE TESTS ARE ON A PASS/FAIL BASIS ONLY. <br /> TANK #1 : REG UNLEADED TYPE: STEEL RATE: .003280 G.P.H. GAIN <br /> ULLAGE: PASS SIGNAL/NOISE: -.01 <br /> TANK IS TIGHT. <br /> TANK #2: SUPER UNLEADED TYPE; STEEL RATE: .007857 G.P.H. GAIN <br /> ULLAGE: PASS SIGNAL/NOISE: .01 <br /> TANK IS TIGHT. <br /> EQUIPMENT: USTEST <br /> OTTL# 97--1143 <br /> OPERATOR: LYLE D. NIMMO SIGNATURE: <br /> DAVID A. WINKLER, Trainee <br />