Laserfiche WebLink
Initial Final Total Gas Initial Meter Final Meter <br /> N=Je Fuel Noale Model&Serial Dispenser Dispenser Time Dispensing Pass/Fail <br /> Number Grade No. ReadingReading Dispensed Reading (ft"), Reading V/L <br /> 9 (gal.(. (sec) Rate(gala V1 (ft'(,VI (P/F1 <br /> al. ,G. (gal.),Gr - <br /> 3 87 7.65 1.06 PASS <br /> 89 6.73 1.04 PASS <br /> 91 8.18 1.06 PASS <br /> 4 87 9.37 1.03 PASS <br /> 89 6.96 1.04 PASS <br /> 91 8.37 1.04 PASS <br /> 5 87 7.50 1.12 PASS <br /> 89 7.39 1.08 PASS <br /> 91 6.36 1.10 PASS <br /> 6 87 7.43 1.07 PASS <br /> 89 7.77 1.07 PASS <br /> 91 6.49 1.09 PASS <br /> 7 87 9.32 1.09 PASS <br /> 89 7.77 1.09 PASS <br /> 91 8.52 1.09 PASS <br /> 8 87 8.62 1.14 PASS <br /> 89 7.96 1.11 PASS <br /> 91 8.82 1.14 PASS <br /> NOTE: The V/L ratio shall be 0.95 to 1.15,measured at a flow rate between 6.0-10.0 gpm. Any fueling point whose V/L ratio is determined to be at or below 0.80 shall be <br /> deemed defective and removed from service. <br /> 1 declare,under penalty of perjury under the laws or the state of Canfomic that based on information and befief formed after reasonable inquiry,the statements and information provided In the document are hue,aocumte,and <br /> complete. <br /> Signature of Technician: Date: 812812018 <br /> %or. L11- 12_'6.117 <br />