Laserfiche WebLink
SWRCB,January 2002 Page L- of <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: Tank Manufacturer ❑Industry Standard L Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure Vacuum ❑Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: Equipment Resolution: <br /> Tank# 1 Tank#2 Tank#3 Tank# <br /> Is"Tank Exempt From Testing?' X Yes No X Yes No X Yes ❑No ❑ Yes ❑No <br /> Tank Capacity: 15K 15K 15K <br /> Tank Material: Fiberglass Fiberglass Fiberglass <br /> Tank Manufacturer: Owens Corning Owens Corning Owens Corning <br /> Product Stored: Regular 87 Supreme 91 Diesel <br /> Wait time between applying Exempt Exempt Exempt <br /> vacuum and starting test: See Comments See Comments See Comments <br /> Test Start Time: <br /> Initial Reading(Rj): <br /> Test End Time: <br /> Final Reading(RF): <br /> Test Duration: <br /> Change in Reading(RF-Ri): <br /> Pass/Fail Threshold or Criteria: <br /> Test Result: Pass ❑Fail Pass ❑Fail ❑ Pass ❑Fail ❑ Pass ❑Fail <br /> Was sensor removed for testing? Yes ❑No ❑NA Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> Was sensor properly replaced and Yes ❑No ❑NA Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> Tanks have Brine filled Annulars, and are exempt from periodic Testing! <br /> Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23, Section 2637(a)(6)) <br />