Laserfiche WebLink
ITTSIntegrity Tank Testing Systems, Inc. <br /> March 24, 1990 <br /> Mr. Charles Leubner <br /> Stockton Unified School District <br /> 1932 North El Pinal <br /> Stockton, California 95205 <br /> Dear Mr. Leubner: <br /> Following is a summary of the precision testing we <br /> recently conducted on your underground storage tank (s) . <br /> Enclosed are copies of the test worksheets and computer <br /> generated data for your submittal to the appropriate <br /> governmental agency. <br /> A tank system is considered tight, according to the <br /> current rules, if the gain/loss is less than .05 gallons per <br /> one hour of testing. If the results are beyond these <br /> parameters, you should consider taking some remedial action. <br /> TANK # OR TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> South 12,000 Diesel -.399 Beyond Parameters <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely, <br /> Frank Reser <br /> Certified Tester <br /> 800 262-8378 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 <br />