Page 1 of 1 <br /> Garrett Backus [EH] <br /> From: Garrett Backus [EH] <br /> Sent: Wednesday, July 21, 2010 4:24 PM <br /> To: 'Dan Mcllrath (vutank@sbcglobal.net)' <br /> Subject: Stockton Unified School District monitoring plans <br /> Attachments: Diesel monitoring plan.pdf; Gasoline monitoring plan.pdf <br /> Hi Dan, <br /> I need a few more corrections. See the attached highlighted copies. <br /> For the Diesel monitoring plan ONLY: <br /> 1) The tank annular sensor model number is "ELS", not"FXIV". <br /> 2) Check the"yes" boxes for the alarm and disconnection triggers shutdown. <br /> 3) In the comments section change the overfill prevention to: "Overfill prevention method is mechanical flapper set <br /> at 95% of tank capacity" <br /> (unless Stockton Unified wants to go to another method —the diesel tank currently has a flapper) <br /> For the Gas monitoring plan ONLY: <br /> 1) The tank annular sensor model number is"ELS", not"FXIV". <br /> 2) Uncheck the visual pipe monitoring box, min. monthly(this is for emergency generator tanks only) <br /> Please correct and return to me. <br /> Thank you, <br /> Garrett Backus <br /> Senior Registered Environmental Health Specialist <br /> San Joaquin County Environmental Health Department <br /> 600 E Main Street, Stockton CA 95202-3029 <br /> telephone: (209)468-2986 <br /> fax: (209)468-3433 <br /> email: gbackus@sjcehd.com <br /> 7/21/2010 <br />