1 <br /> modern we.,,ng,company <br /> modern <br /> INSTALLATION PROCEDURES FOR UNDERGROUND STORAGE TANKS <br /> CAUTION ; N. F. P. A. -30 : TIGHTNESS TESTING REQUIREMENTS : IT IS THE RESPONSIBILITY <br /> OF THE D11NER TO PROVIDE THE FOLLOWING TESTS PRIOR TO 'COVERING THE TAWS) . <br /> N.F.P.A.-30; 2-7.3: "Underground tanks and piping, before being covered, enclosed, or <br /> placed in use, shall be tested for tightness hydrostatically, or <br /> with air pressure at not less than 3-PSI, and more than 5-PSI." <br /> H.F.P.A.-30; 2-7.4: "Before the tank is initially placed in service, all leaks shall be <br /> corrected in an acceptable manner." <br /> N.F.P.A.-31 "Standard for Installation of Oil Burning Equipment." <br /> NOTE: YOUR STATE OR LOCAL CODES MAY REQUIRE PROTECTED PIPING SYSTEMS? <br /> TANK HANDLING: <br /> UNDERGROUND TANK(S) ARE SUPPLIED WITH EITHER ONE OR TWO INSTALLED LIFTING LUGS, DEPENDENT ON TANK SIZE. <br /> REFER TO SPECIFIC TANK DRAWING TO DETERMINE THE EMPTY LIFTING WEIGHT OF THE TANK. <br /> SEE "FINISHING INSTRUCTIONS", ITEM NUMBER 7; FOR APPLICATION OF LIFTING LUG COVERS TO "GLASTEEL" TANKS PRIOR <br /> TO BACKFILLING OR COVERING THE TANK. <br /> DO NOT DROP OR ROLL TANK(S) FROM TRUCK INTO EXCAVATED OPENING. <br /> HOLE SI7_ES FOR INSTALLATION OF TANKS IN STABLE SOIL CONDITIONS: <br /> ,GENERAL NOTES: <br /> 1 . T}lE EXCAVATED OPENING FOR INSTALLATION OF UNDERGROUND TANK(S) SHALL BE SUITABLY EXCAVATED (REFER TO OSHA, <br /> STATE, OR LOCAL CODES GOVERNING OPENINGS) , LEVELED AND BACKFILLED PER THE FOLLOWING INSTRUCTIONS. <br /> 2. REFER TO THE "FINISHING INSTRUCTIONS" FOR SPECIAL P.EQUIREMENTS PRIOR TO BURIAL OF "GLASTEEL" TANKS. <br /> 3. TANKS SHALL BE CCMPLETLY EMPTY DURING HANDLING OR INSTALLATION TO PREVENT UNDUE STRESS TO THE TANK(S). <br /> 4. IN THE EVENT A TANK MUST BE INSTALLED, FILLED WITH PRODUCTS, PRIOR TO BACKFILLING, THE LIQUID LEVEL WITHIN <br /> THE TANK SHALL NOT EXCEED THE COMPACTED BACKFILL LEVEL. <br /> CONCRETE, ASPHALT, <br /> OR COMPACTED SOIL NOTE"A", THE FOUNDATION FOR UNDERGROUND TANK(S) SHALL BE A <br /> MINIMUM OF 6" CLEAN CC61PACTED SAND, 6" OF 3/4'• PEA <br /> NOTE"C1" GRAVEL, OR CLEAN COMPACTED SOIL. <br /> iv NOTE"B1". TANK(S) INSTALLED IN AN AREA THAT IS SUBJECT TO <br /> HEAVY VEHICULAR TRAFFIC SHALL HAVE A PROTECTIVE <br /> glgNI COVER OF 18" CLEAN COMPACTED SOIL WITH EITHER <br /> 0 <br /> LU w 6" OF REINFORCED CONCRETE, OR 8" OF ASPHALT <br /> QL PAVING. IF COMPACTED SOIL IS TO BE THE ONLY COVER <br /> ;x' •• IT SHALL BE A MINIMUM OF 36" DEEP, <br /> 0 <br /> NOTE"82". TANK(S) INSTALLED IN AN AREA NOT SUBJECT TO HEAVY <br /> CROSSECTION OF EXCAVATION VEHICULAR TRAFFIC SHALL BE PROTECTED WITH EITHER <br /> 24" OF CLEAN COMPACTED SOIL, OR 18" OF CLEAN <br /> COMPACTED SOIL COVERED BY 4" THICK REINFORCED <br /> .J.I CONCRETE OR 6" THICK ASPHALT PAVING. <br /> NOTE"C1". SINGLE TANK INSTALLATION: MINIMUM OF 12" FROM THE <br /> o UjUj <br /> LU g OUTSIDE EDGE OF TANK TO THE INSIDE EDGE OF THE <br /> EXCAVATED OPENING. <br /> F- <br /> N <br /> o NOTE"C2". MULTIPLE TANK INSTALLATION: SAME EDGE DISTANCES <br /> M �,I I AS SINGLE TANK INSTALLATION, AND A MINIMUM OF 12" <br /> FROM OUTSIDE EDGE TO OUTSIDE EDGE OF THE TANKS. <br /> NOTE"C2" NOT "D" NOTE"D", THE MINIMUM,DISTANCE FROM THE OUTSIDE ENDS OF THE <br /> TANK(S) TO THE INSIDE EDGE OF THE OPENING SHALL BE, <br /> PLAN ATPIJLTIPI.E TANK INSTALLATION A MINIMUM OF 12", <br /> Page 1 of 2 <br />